Skip to main content
Siemens 3RA2210-1GS15-2BB4 — Motor Starters

Siemens 3RA2210-1GS15-2BB4 Reversing Starter, S00

MPN3RA2210-1GS15-2BB4
Active

Siemens SIRIUS 3RA2210-1GS15-2BB4 reversing starter, size S00, 2.2 kW at 400 V AC-3, Class 10, spring-loaded terminals, 60 mm busbar snap-on mounting.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA2210-1GS15-2BB4 — Identification
ParameterValue
Product designationReversing starter
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructionfor 60 mm busbars
Circuit-breaker sizeS00
Included contactor (type)3RT2015-2BB42
Included circuit-breaker (type)3RV2011-1GA20
Included link module (type)3RA2911-2AA00

Ratings & Performance

3RA2210-1GS15-2BB4 — Ratings & Performance
ParameterValue
Rated motor power at 400 V2 200 W
Operational current Ie, AC-3 at 400 V4.9 A
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)3 hp
Rated motor power at 575/600 V (hp)5 hp
Rated current at 480 V4.8 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)30 000 000

Protection & Tripping

3RA2210-1GS15-2BB4 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)150 000 A
Overload release setting range (current)4.5 ... 6.3 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)1

Contacts & Control

3RA2210-1GS15-2BB4 — Contacts & Control
ParameterValue
Rated value24 ... 24 V
Control supply voltage typeDC
Auxiliary switch extensionYes
Switching contact typeelectromechanical

Communication

3RA2210-1GS15-2BB4 — Communication
ParameterValue
AS-Interface protocol supportNo

Mechanical & Connection

3RA2210-1GS15-2BB4 — Mechanical & Connection
ParameterValue
Mounting / fastening methodfor snapping onto 60 mm busbar systems
Mounting positionvertical
Width90 mm
Height212 mm
Depth155 mm

Environmental

3RA2210-1GS15-2BB4 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-50 ... +80 °C
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

Reversing starter that snaps onto 60 mm busbars

The 3RA2210-1GS15-2BB4: It comes as a pre-assembled unit: the supplied 3RT2015-2BB42 contactor, 3RA2911-2AA00 link module, and 8US1251-5DS11 busbar adapter mount directly onto 60 mm busbar systems via the snap-on fastening method.

Spring terminals and clearance for panel planning

Main circuit connections use spring-loaded terminals — no screwdriver torque check, no loose lugs after a vibration cycle. The unit is 155 mm deep, 90 mm wide, 212 mm tall, and mounts vertically. Clearance requirements: 50 mm upwards, 32 mm forwards, 10 mm downwards, 10 mm at the side, and 0 mm backwards — that zero backward clearance means the back of the housing can sit flush against the panel backplate. Operating temperature range is -20 to +60 °C, with temperature compensation built into the overload curve across that span. Storage and transport limits extend from -50 to +80 °C.

Motor power coverage across common line voltages

At 480 V the rated current is 4.8 A. The maximum AC-3 operating voltage is 690 V, and frequency is 50/60 Hz. The overload release is thermal bimetallic — no electronic adjustment, no auxiliary power needed for the trip curve. This keeps the assembly simple and field-reliable: if the bimetals heat up, the starter opens; when they cool, it resets.

Active production, sourced per RFQ

Substance prohibition date per RoHS is 10/01/2009 — the starter complies with the original RoHS directive. No REACH or UL certificate numbers are on the spec record; the buyer should request the Siemens declaration of conformity for their compliance file.

Frequently asked questions

What motor power does 3RA2210-1GS15-2BB4 cover at 400 V?

At 480 V it handles 3 hp at 4.8 A, and at 575/600 V it goes up to 5 hp.

What is the mounting method for this reversing starter?

It snaps onto 60 mm busbar systems using the supplied 8US1251-5DS11 busbar adapter. Mounting position is vertical. Clearance: 50 mm above, 32 mm front, 10 mm below, 10 mm sides, 0 mm behind.

MPN
3RA2210-1GS15-2BB4