Reversing starter in a S00 frame — what the ratings mean on the line
This 3RA2210-1JD16-2AK6 is a SIRIUS non-fused load feeder configured as a reversing starter — meaning it combines a contactor pair and a thermal overload relay in one unit sized S00, ready to reverse a three-phase motor without external interlocking wiring. The 7.6 A at 480 V and 9 A at 600 V give you the current ceiling for conductor sizing.
Snap-on busbar mounting and panel fit
Mounts by snapping directly onto a 60 mm busbar system — no DIN rail adapter needed, which saves a rail slot and keeps the busbar run continuous. The vertical mounting position is specified; horizontal mounting would change the thermal calibration of the bimetallic release. Dimensions are 155.1 mm deep × 90 mm wide × 200 mm tall. Clearance requirements: 20 mm upwards, 10 mm downwards, 9 mm at the sides, and zero forwards or backwards — so it fits tight against the back panel and the enclosure door. The supplied contactor is a 3RT2016-1AK62 and the link module is 3RA1921-1DA00 — these are the matched components inside the assembly, so ordering the feeder as a single code saves you sourcing three separate line items.
Lifecycle and sourcing — current production, quoted to order
Operating temperature range is -20 to +60 °C, storage and transport range -50 to +80 °C. Pollution degree 3 means it is rated for industrial environments with conductive pollution — typical for control panels without climate control. Substance prohibitance date of 10/01/2009 indicates RoHS compliance per the EU directive effective date — the part is RoHS-compliant for current builds.