Reversing starter, S00 frame, 9 A AC-3 at 400 V
The 3RA2210-1JD16-2BB4: It ships with the 3RT2016-1BB42 contactor and the 3RA1921-1DA00 link module — a pre-assembled pair that handles the interlocking for reversing, so you do not have to wire mechanical interlocks yourself.
Snaps onto 60 mm busbar systems — panel layout notes
The fastening method is snap-on for 60 mm busbar systems, with a vertical mounting position specified. That means it clips directly onto the standard busbar riser in a distribution panel — no DIN rail adapter needed. Dimensions are 155 mm deep, 90 mm wide, 204 mm tall. Clearances: 50 mm upward, 32 mm forward, 10 mm downward, 10 mm at the side, and 0 mm backward — so the back can sit flush against the panel backplane. Main circuit connections are screw-type terminals, which means field wiring with ring or fork lugs — no special crimp tool required.
Active production — sourcing posture
No stock-holding claim — quantities are quoted per BOM.