Siemens 3RA2210-1KD17-2AP6 Reversing Motor Starter, S00

MPN3RA2210-1KD17-2AP6

Siemens SIRIUS 3RA2210-1KD17-2AP6 non-fused reversing motor starter, size S00, CLASS 10 thermal bimetallic overload, 5.5 kW at 400 V, 11 A at 480 V, 690 V max, snaps onto 60 mm busbar.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA2210-1KD17-2AP6 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructionreversing starter
Circuit-breaker sizeS00
Included contactor (type)3RT2017-1AP62
Included circuit-breaker (type)3RV2011-1KA10
Included link module (type)3RA1921-1DA00

Ratings & Performance

3RA2210-1KD17-2AP6 — Ratings & Performance
ParameterValue
Rated motor power at 400 V5 500 W
Operational current Ie, AC-3 at 400 V11.5 A
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)7.5 hp
Rated motor power at 575/600 V (hp)10 hp
Rated current at 480 V11 A
Rated current at 600 V11 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V

Protection & Tripping

3RA2210-1KD17-2AP6 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)9 ... 12.5 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)1

Contacts & Control

3RA2210-1KD17-2AP6 — Contacts & Control
ParameterValue
Rated value690 V
Rated voltage range at 50 Hz187 ... 242 V
Auxiliary contacts, NC1
Auxiliary switch extensionYes
Switching contact typeelectromechanical

Mechanical & Connection

3RA2210-1KD17-2AP6 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Mounting / fastening methodfor snapping onto 60 mm busbar systems
Mounting positionvertical
Width90 mm
Height200 mm
Depth155.1 mm

Environmental

3RA2210-1KD17-2AP6 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

Reversing starter for S00 load feeders

The 3RA2210-1KD17-2AP6 is a non-fused reversing motor starter from the Siemens SIRIUS family, built in the S00 frame size. It combines a contactor and a thermal bimetallic overload relay in one unit, wired for reversing duty — forward and reverse contactors interlocked mechanically and electrically. Rated motor power spans from 0.5 hp at 110/120 V up to 10 hp at 575/600 V, with the 400 V rating at 5.5 kW. The AC-3 switching voltage maxes out at 690 V, covering most low-voltage three-phase motor circuits.

CLASS 10 thermal overload — what it means for motor protection

For a motor that starts under load — conveyor, crusher, pump — this is the standard class; it clears a stalled rotor fast enough to keep the motor winding within its thermal limit while tolerating normal acceleration. The overload release is thermal bimetallic, so it tracks the motor's I²t heating curve without an external CT. Ambient compensation is built in for the -20 to +60 °C operating range.

Snap-on busbar mounting and panel clearances

Mounts by snapping onto 60 mm busbar systems — no screws or DIN rail adapter needed. The mounting position is vertical only; horizontal mounting is not supported. Dimensions: 200 mm height, 90 mm width, 155.1 mm depth. Clearance requirements: 20 mm upwards, 10 mm downwards, 9 mm at the side, zero forwards and backwards. Pollution degree 3 means it handles conductive dust and humidity typical of industrial control panels.

Active production — sourcing posture

The unit ships with the contactor 3RT2017-1AP62 and link module 3RA1921-1DA00 pre-assembled. RoHS compliance date is 03/01/2017.

Frequently asked questions

What is the motor power rating of 3RA2210-1KD17-2AP6 at 400 V?

At 400 V rated value, it delivers 5.5 kW. At 480 V it is rated 11 A, and at 600 V also 11 A. The maximum AC-3 switching voltage is 690 V.

What trip class is the overload relay on 3RA2210-1KD17-2AP6?

The overload release is thermal bimetallic.

What clearance is needed around 3RA2210-1KD17-2AP6 in the panel?

Required clearances: 20 mm upwards, 10 mm downwards, 9 mm at the side. Zero clearance needed forwards or backwards. Dimensions are 200 mm high, 90 mm wide, 155.1 mm deep.