Skip to main content
Siemens 3RA2215-0AD15-2BB4 — Motor Starters

Siemens 3RA2215-0AD15-2BB4 SIRIUS Reversing Starter, S00

MPN3RA2215-0AD15-2BB4

Siemens SIRIUS 3RA2215-0AD15-2BB4 non-fused reversing motor starter, size S00, 24 VDC coil, Class 10, 3-pole, 155.1 mm depth, 90 mm width, 200 mm height.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RA2215-0AD15-2BB4 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructionreversing starter
Circuit-breaker sizeS00
Included contactor (type)3RT2015-1BB42
Included circuit-breaker (type)3RV2011-0AA15
Included link module (type)3RA1921-1DA00
3RA2215-0AD15-2BB4 — Ratings & Performance
ParameterValue
Rated motor power at 400 V40 W
Operational current Ie, AC-3 at 400 V0.16 A
Rated voltage at AC-3, max.690 V
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
3RA2215-0AD15-2BB4 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)0.11 ... 0.16 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2
3RA2215-0AD15-2BB4 — Contacts & Control
ParameterValue
Rated value24 V
Auxiliary contacts, NO1
Auxiliary contacts, NC2
Auxiliary switch extensionYes
Switching contact typeelectromechanical
3RA2215-0AD15-2BB4 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Mounting / fastening methodfor snapping onto 60 mm busbar systems
Mounting positionvertical
Width90 mm
Height200 mm
Depth155.1 mm
3RA2215-0AD15-2BB4 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

What ships in the box — pre-assembled components

The 3RA2215-0AD15-2BB4 arrives as a fully assembled reversing starter: it includes the supplied contactor (3RT2015-1BB42), the link module (3RA1921-1DA00), the circuit-breaker (3RV2011-0AA15), the busbar adapter (8US1251-5DS10), and the RS assembly kit (3RA2913-1DB1). No piece-part sourcing needed — one order code, one package.

Rated for reversing duty — AC-3 at 690 V

Power dissipation at 400 V and 500 V is 40 W; at 690 V it rises to 60 W, so panel thermal budget needs that margin. The 24 VDC coil draws 4 W holding power — a standard PLC digital output can drive it directly through an interposing relay if the output card is rated for the inrush.

Mounting and panel fit — snaps onto 60 mm busbar

Fastening method is for snapping onto 60 mm busbar systems — no DIN-rail adapter needed if the panel uses busbar mounting. Mounting position is vertical only. Dimensions: 155.1 mm depth, 90 mm width, 200 mm height. Clearance required: 20 mm upwards, 10 mm downwards, 9 mm at the side.

Trip class and environmental limits

Operating temperature range is -20 to +60 °C; storage range is -50 to +80 °C; transport range is -55 to +80 °C. Pollution degree 3 (conductive pollution or dry non-conductive that becomes conductive).

Frequently asked questions

How do I get current pricing and availability for 3RA2215-0AD15-2BB4?

Submit an RFQ through this listing.

MPN
3RA2215-0AD15-2BB4