What ships in the box — pre-assembled components
The 3RA2215-0AD15-2BB4 arrives as a fully assembled reversing starter: it includes the supplied contactor (3RT2015-1BB42), the link module (3RA1921-1DA00), the circuit-breaker (3RV2011-0AA15), the busbar adapter (8US1251-5DS10), and the RS assembly kit (3RA2913-1DB1). No piece-part sourcing needed — one order code, one package.
Rated for reversing duty — AC-3 at 690 V
Power dissipation at 400 V and 500 V is 40 W; at 690 V it rises to 60 W, so panel thermal budget needs that margin. The 24 VDC coil draws 4 W holding power — a standard PLC digital output can drive it directly through an interposing relay if the output card is rated for the inrush.
Mounting and panel fit — snaps onto 60 mm busbar
Fastening method is for snapping onto 60 mm busbar systems — no DIN-rail adapter needed if the panel uses busbar mounting. Mounting position is vertical only. Dimensions: 155.1 mm depth, 90 mm width, 200 mm height. Clearance required: 20 mm upwards, 10 mm downwards, 9 mm at the side.
Trip class and environmental limits
Operating temperature range is -20 to +60 °C; storage range is -50 to +80 °C; transport range is -55 to +80 °C. Pollution degree 3 (conductive pollution or dry non-conductive that becomes conductive).