The 3RA2215-0ED15-2AP6: This is a non-fused reversing motor starter, Size S00, meaning it combines a forward and reverse contactor with a thermal overload relay in a single assembly that reverses a three-phase motor without external interlocking wiring. Rated 690 V AC-3 maximum, so it handles the full motor-switching duty on 400 V and 480 V systems with headroom; the 690 V ceiling covers 575 V line-line installations common in Canadian and mining applications.
Supplied sub-assemblies — what comes in the box
The starter ships with the 3RT2015-1AP62 contactor, 3RA1921-1DA00 link module, 8US1251-5DS10 busbar adapter, 3RA2913-1DB1 RS assembly kit, and 3RV2011-0EA15 circuit-breaker — all pre-assembled and coordinated for the S00 frame. The supplied circuit-breaker provides the magnetic short-circuit trip; the thermal overload release in the link module handles the Class 10 protection curve.
Mounting and integration — busbar snap-on fit
Snaps directly onto 60 mm busbar systems via the supplied busbar adapter — no DIN rail required for the power side, which saves a rail and reduces panel depth. Vertical mounting position only; the dimensions are 200 mm height, 90 mm width, 155.1 mm depth — the 90 mm width is the critical panel cutout dimension for multi-starter layouts. Clearance spaces: 20 mm upwards, 10 mm downwards, 9 mm at the side — zero forwards or backwards clearance needed, so it can sit flush against the back panel or enclosure wall.