Skip to main content
Siemens 3RA2215-0FA15-2AK6 — Motor Starters

Siemens 3RA2215-0FA15-2AK6 SIRIUS Reversing Starter

MPN3RA2215-0FA15-2AK6

Siemens SIRIUS reversing motor starter, 3RA2215-0FA15-2AK6, S00 size, CLASS 10 thermal overload, 690 V rated, 50/60 Hz, snap-on DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RA2215-0FA15-2AK6 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructionreversing starter
Circuit-breaker sizeS00
Included contactor (type)3RT2015-1AK62
Included circuit-breaker (type)3RV2011-0FA15
Included link module (type)3RA1921-1DA00
3RA2215-0FA15-2AK6 — Ratings & Performance
ParameterValue
Rated motor power at 400 V120 W
Operational current Ie, AC-3 at 400 V0.4 A
Rated voltage at AC-3, max.690 V
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)30 000 000
3RA2215-0FA15-2AK6 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)0.35 ... 0.5 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2
3RA2215-0FA15-2AK6 — Contacts & Control
ParameterValue
Rated value690 V
Rated voltage range at 50 Hz93.5 ... 121 V
Auxiliary contacts, NO1
Auxiliary contacts, NC2
Auxiliary switch extensionYes
Switching contact typeelectromechanical
3RA2215-0FA15-2AK6 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
Mounting / fastening methodSnap-mounted to DIN rail or screw-mounted with additional push-in lug
Mounting positionvertical
Width90 mm
Height170 mm
Depth97.1 mm
3RA2215-0FA15-2AK6 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

The Siemens SIRIUS 3RA2215-0FA15-2AK6 is a non-fused reversing motor starter in size S00, combining a contactor, thermal overload relay, and circuit-breaker into one assembly for forward/reverse motor control in a compact footprint. Rated for AC-3 duty up to 690 V and 50/60 Hz, the CLASS 10 trip class means it protects standard squirrel-cage motors during start-up without nuisance tripping on normal acceleration — a common spec for conveyor and pump reversing applications. Snap-mounted to DIN rail or screw-mounted with an additional push-in lug, this unit fits standard 90 mm wide panel slots and requires 170 mm vertical clearance plus 20 mm above and 10 mm below for wiring access.

It ships as a complete assembly with the supplied contactor (3RT2015-1AK62), link module (3RA1921-1DA00), and circuit-breaker (3RV2011-0FA15) — no separate component sourcing needed for the reversing function.

Integration Notes

Mounting position is vertical only; the thermal overload release (bimetallic) is calibrated for that orientation and may drift if mounted horizontally. Main contact wiring accepts 0.5 to 4 mm² stranded or 2x (0.75 to 2.5 mm²) — use ferrules on stranded wire to avoid whiskers under the cage terminals. Surge voltage resistance rated at 6 kV, suitable for industrial environments with pollution degree 3 — typical for panels near motors and drives without additional suppression.

Frequently asked questions

How do I get current pricing and availability for 3RA2215-0FA15-2AK6?

Pricing and availability are confirmed at quote time against an RFQ through independent distribution channels — submit an RFQ for a current quote and lead time.

Is 3RA2215-0FA15-2AK6 compatible with 24 VDC coil?

The evidence does not list the coil voltage for this specific order code. The supplied contactor (3RT2015-1AK62) determines coil compatibility — check its datasheet for the coil rating.

How do I wire 3RA2215-0FA15-2AK6?

Main contact wiring accepts 0.5 to 4 mm² stranded or 2x (0.75 to 2.5 mm²). Use the supplied circuit-breaker (3RV2011-0FA15) for short-circuit protection and the thermal overload for motor protection. Auxiliary switch expansion is available for feedback.

MPN