Skip to main content
Siemens 3RA2215-0HA15-2AP6 — Motor Starters

Siemens 3RA2215-0HA15-2AP6 Reversing Motor Starter, S00

MPN3RA2215-0HA15-2AP6

Siemens SIRIUS 3RA2215-0HA15-2AP6 non-fused reversing motor starter, size S00, Class 10 thermal overload relay, 180 W at 400 V, 50/60 Hz, snap-on DIN rail mount.

StockIn Stock (47)
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026Stock-verified to date
How we verify every order →

Specifications

Identification

3RA2215-0HA15-2AP6 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructionreversing starter
Circuit-breaker sizeS00
Included contactor (type)3RT2015-1AP62
Included circuit-breaker (type)3RV2011-0HA15
Included link module (type)3RA1921-1DA00

Ratings & Performance

3RA2215-0HA15-2AP6 — Ratings & Performance
ParameterValue
Rated motor power at 400 V180 W
Operational current Ie, AC-3 at 400 V0.6 A
Rated voltage at AC-3, max.690 V
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)30 000 000

Protection & Tripping

3RA2215-0HA15-2AP6 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)0.55 ... 0.8 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2

Contacts & Control

3RA2215-0HA15-2AP6 — Contacts & Control
ParameterValue
Rated value690 V
Rated voltage range at 50 Hz187 ... 242 V
Auxiliary contacts, NO1
Auxiliary contacts, NC2
Auxiliary switch extensionYes
Switching contact typeelectromechanical

Mechanical & Connection

3RA2215-0HA15-2AP6 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
Mounting / fastening methodSnap-mounted to DIN rail or screw-mounted with additional push-in lug
Mounting positionvertical
Width90 mm
Height170 mm
Depth97.1 mm

Environmental

3RA2215-0HA15-2AP6 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

Reversing starter for tight panels

The 3RA2215-0HA15-2AP6: This is a Siemens SIRIUS 3RA2 non-fused reversing motor starter — a pre-assembled unit that combines a contactor, thermal overload relay, and short-circuit protection in one size S00 package. It's built for controlling reversing motor loads like conveyors, hoists, or valve actuators where you need forward/reverse switching without separate component wiring. Rated 180 W at 400 V and 370 W at 690 V, with a 50/60 Hz operating range. Snaps onto DIN rail or screws down with the included push-in lug. Mounting is vertical only — horizontal mounting changes the thermal behavior and voids the overload calibration. Dimensions: 170 mm tall, 90 mm wide, 97.1 mm deep, with 20 mm clearance needed above and 10 mm below for airflow and wiring.

What's inside the box — supplied components

The starter ships as a complete assembly: a 3RT2015-1AP62 contactor, a 3RA1921-1DA00 link module, and a 3RV2011-0HA15 circuit-breaker. That means the overload relay and magnetic short-circuit trip are already wired and coordinated — no guessing on the trip curve match. The contactor is electromechanical, the overload is thermal bimetallic, and the short-circuit trip is magnetic. Pollution degree 3 rated — fine for industrial control panels where dust and conductive deposits are present. AWG equivalents: 2x 20–16, or 2x 18–14, or 2x 12. The auxiliary switch extension is available (product extension auxiliary switch: Yes) if you need feedback to the PLC.

Active production — sourcing this exact code

No stock-holding claim — sourced per RFQ.

Frequently asked questions

What are the power ratings at different voltages for this motor starter?

At 400 V it's rated 180 W, at 500 V it's 250 W, and at 690 V it's 370 W.

What mounting clearances are needed around this starter?

Requires 20 mm clearance above, 10 mm below, 9 mm at the sides, and 0 mm forward/backward. Mounting is vertical only, snap-on DIN rail or screw mount with the included push-in lug.

MPN
3RA2215-0HA15-2AP6