Skip to main content
Siemens 3RA2215-1BD15-2AP6 — Motor Starters

Siemens 3RA2215-1BD15-2AP6 SIRIUS Reversing Starter

MPN3RA2215-1BD15-2AP6

Siemens SIRIUS 3RA2215-1BD15-2AP6 non-fused reversing motor starter, size S00, 750 W at 400 V AC-3, thermal Class 10, 690 V max, snap-on 60 mm busbar.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RA2215-1BD15-2AP6 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructionreversing starter
Circuit-breaker sizeS00
Included contactor (type)3RT2015-1AP62
Included circuit-breaker (type)3RV2011-1BA15
Included link module (type)3RA1921-1DA00
3RA2215-1BD15-2AP6 — Ratings & Performance
ParameterValue
Rated motor power at 400 V750 W
Operational current Ie, AC-3 at 400 V1.9 A
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)0.75 hp
Rated motor power at 575/600 V (hp)1 hp
Rated current at 480 V1.63 A
Rated current at 600 V1.72 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)30 000 000
3RA2215-1BD15-2AP6 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)1.4 ... 2 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2
3RA2215-1BD15-2AP6 — Contacts & Control
ParameterValue
Rated value690 V
Rated voltage range at 50 Hz187 ... 242 V
Auxiliary contacts, NO1
Auxiliary contacts, NC2
Auxiliary switch extensionYes
Switching contact typeelectromechanical
3RA2215-1BD15-2AP6 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
Mounting / fastening methodfor snapping onto 60 mm busbar systems
Mounting positionvertical
Width90 mm
Height200 mm
Depth155.1 mm
3RA2215-1BD15-2AP6 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

Form factor and panel fit — S00 reversing starter on 60 mm busbar

The 3RA2215-1BD15-2AP6 is a SIRIUS size S00 reversing motor starter — 200 mm tall, 90 mm wide, 155.1 mm deep — designed to snap directly onto a 60 mm busbar system, not a DIN rail. Mounting is vertical only; the enclosure requires 20 mm clearance upward and 10 mm downward, with 9 mm side clearance for airflow and wiring access. The unit ships as a pre-assembled reversing combination: the supplied contactor (3RT2015-1AP62), link module (3RA1921-1DA00), and busbar adapter (8US1251-5DS10) are included, so no separate ordering of sub-components for the reversing function.

Motor ratings and trip class — what the 750 W at 400 V means for your load

At 480 V the full-load current rating is 1.63 A; at 600 V it is 1.72 A. The control coil is rated for 187–242 V at 50 Hz and 192–264 V at 60 Hz — a wide-range coil that covers 200–240 V line voltages across both mains frequencies without a tap change.

Wire termination and environmental limits

Operates from -20 to +60 °C ambient; storage range -50 to +80 °C; transport range -55 to +80 °C. Pollution degree 3 (conductive pollution or dry non-conductive that becomes conductive due to condensation — typical in industrial control cabinets without climate control).

Lifecycle and sourcing — active, quoted to order

No stock-holding claim is made — each RFQ is handled individually.

Frequently asked questions

What is the 3RA2215-1BD15-2AP6 rated for at 400 V?

At 400 V AC-3 it is rated 750 W. The maximum operating voltage is 690 V AC-3, and the thermal overload is Class 10 bimetallic.

Does the 3RA2215-1BD15-2AP6 mount on DIN rail or a busbar?

It snaps onto a 60 mm busbar system, not a standard DIN rail. The mounting position must be vertical.

What components are supplied with the 3RA2215-1BD15-2AP6?

The unit includes the contactor (3RT2015-1AP62), link module (3RA1921-1DA00), and busbar adapter (8US1251-5DS10) — it ships as a complete reversing starter assembly.

MPN
3RA2215-1BD15-2AP6