Skip to main content
Siemens 3RA2215-1CD15-2BB4 — Motor Starters

Siemens 3RA2215-1CD15-2BB4 Reversing Motor Starter, S00

MPN3RA2215-1CD15-2BB4

Siemens SIRIUS 3RA2215-1CD15-2BB4 non-fused reversing motor starter, size S00, 24 VDC coil, Class 10 thermal bimetallic overload, 750 W at 400 V AC-3, 50/60 Hz, snap-on 60 mm busbar.

$102.87Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RA2215-1CD15-2BB4 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructionreversing starter
Circuit-breaker sizeS00
Included contactor (type)3RT2015-1BB42
Included circuit-breaker (type)3RV2011-1CA15
Included link module (type)3RA1921-1DA00
3RA2215-1CD15-2BB4 — Ratings & Performance
ParameterValue
Rated motor power at 400 V750 W
Operational current Ie, AC-3 at 400 V1.9 A
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)1 hp
Rated motor power at 575/600 V (hp)1.5 hp
Rated current at 480 V2.15 A
Rated current at 600 V2.24 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)30 000 000
3RA2215-1CD15-2BB4 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)1.8 ... 2.5 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2
3RA2215-1CD15-2BB4 — Contacts & Control
ParameterValue
Rated value24 V
Auxiliary contacts, NO1
Auxiliary contacts, NC2
Auxiliary switch extensionYes
Switching contact typeelectromechanical
3RA2215-1CD15-2BB4 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
Mounting / fastening methodfor snapping onto 60 mm busbar systems
Mounting positionvertical
Width90 mm
Height200 mm
Depth155.1 mm
3RA2215-1CD15-2BB4 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

Reversing starter, size S00 — what ships inside

The 3RA2215-1CD15-2BB4 is a SIRIUS non-fused reversing motor starter in frame size S00. It ships as a pre-assembled unit containing a 3RT2015-1BB42 contactor, a thermal bimetallic overload relay (Class 10), a link module 3RA1921-1DA00, and a busbar adapter 8US1251-5DS10 — one order code, one BOM line. The 24 VDC coil keeps the control circuit isolated from the motor power path.

Mounting and clearance — busbar snap-on, vertical only

Snaps directly onto 60 mm busbar systems — no DIN rail adapter needed for the busbar mount. The mounting position is vertical only; the unit is 200 mm tall, 90 mm wide, and 155.1 mm deep. Clearance requirements: 20 mm upwards, 10 mm downwards, 9 mm at the side, zero forwards or backwards. These are the minimum air gaps for heat dissipation and arc containment.

Wire sizing and environmental limits

Operates from -20 to +60 °C, stores from -50 to +80 °C, and survives transport from -55 to +80 °C. Pollution degree 3 rating means it is suitable for industrial environments with conductive dust or occasional condensation.

Lifecycle and sourcing — active, quoted to order

Sourced through authorized distribution channels against the BOM quantity.

MPN
3RA2215-1CD15-2BB4