The 3RA2215-1GD15-2AK6 is a non-fused reversing motor starter in the SIRIUS Size S00 frame — a factory-assembled combination of a 3RT2015 contactor and a thermal bimetallic overload relay, pre-wired for reversing duty. The coil operates on 93.5–121 V at 50 Hz or 96–132 V at 60 Hz — a standard 110/120 V control transformer secondary covers both ranges without a tap change.
Snap-on busbar mounting and panel integration
Fastening method is snap-on for 60 mm busbar systems — no DIN rail adapter needed; the starter clips directly onto the busbar support, saving a mounting step and reducing panel depth. Dimensions are 155.1 mm deep, 90 mm wide, 200 mm tall — the S00 frame width is the critical panel layout dimension; plan for 9 mm side clearance and 20 mm upward clearance for air circulation and wiring access. Mounting position is vertical only — horizontal orientation changes the thermal overload characteristic and voids the trip class rating.
Lifecycle and sourcing — current production, quoted to order
The supplied link module (3RA1921-1DA00) and contactor (3RT2015-1AK62) are standard SIRIUS components, so replacement parts and spares are available through the same distribution channel.