Siemens SIRIUS 3RA2215-1HD16-2AP6 reversing motor starter, Size S00, CLASS 10, 690 V AC-3, 90 mm width, 200 mm height, 155.1 mm depth, snap-on 60 mm busbar.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA2215-1HD16-2AP6 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructionreversing starter
Circuit-breaker sizeS00
Included contactor (type)3RT2016-1AP62
Included circuit-breaker (type)3RV2011-1HA15
Included link module (type)3RA1921-1DA00

Ratings & Performance

3RA2215-1HD16-2AP6 — Ratings & Performance
ParameterValue
Rated motor power at 400 V3 000 W
Operational current Ie, AC-3 at 400 V6.5 A
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)5 hp
Rated motor power at 575/600 V (hp)5 hp
Rated current at 480 V7.6 A
Rated current at 600 V6.33 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)30 000 000

Protection & Tripping

3RA2215-1HD16-2AP6 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)5.5 ... 8 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)1

Contacts & Control

3RA2215-1HD16-2AP6 — Contacts & Control
ParameterValue
Rated value690 V
Rated voltage range at 50 Hz187 ... 242 V
Auxiliary contacts, NO1
Auxiliary contacts, NC2
Auxiliary switch extensionYes
Switching contact typeelectromechanical

Mechanical & Connection

3RA2215-1HD16-2AP6 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
Mounting / fastening methodfor snapping onto 60 mm busbar systems
Mounting positionvertical
Width90 mm
Height200 mm
Depth155.1 mm

Environmental

3RA2215-1HD16-2AP6 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

Active production — what that means for your BOM line

The 3RA2215-1HD16-2AP6: This is a SIRIUS reversing starter, Size S00, designed for motor loads up to 690 V AC-3. The reversing configuration means two contactors interlocked mechanically and electrically, so the motor direction swaps without a separate reversing contactor pair.

Panel fit — dimensions and mounting that matter

Width is 90 mm, height 200 mm, depth 155.1 mm. That 90 mm width is the key panel-space number — it's the same footprint as the S00 contactor and breaker it integrates. Mounting is snap-on onto 60 mm busbar systems — no screws, no DIN rail adapter. The vertical mounting position is required for proper thermal performance. Clearance distances: 20 mm upwards, 10 mm downwards, 9 mm at the side. Zero forwards or backwards clearance needed — the housing is self-contained.

What's in the box — supplied components

The reversing starter ships with the contactor 3RT2016-1AP62 and the link module 3RA1921-1DA00 already integrated. No separate ordering of interlock kits or busbars. That covers most motor feeder sizes up to the rating.

Environmental and pollution rating

Operates from -20 to +60 °C, stores from -50 to +80 °C, transports from -55 to +80 °C. The degree of pollution is 3 — conductive pollution or dry non-conductive pollution that becomes conductive due to condensation. That's typical for industrial control panels without climate control.

Frequently asked questions

What are the key power ratings for 3RA2215-1HD16-2AP6 at different voltages?

At 400 V it's rated 3000 W, at 500 V it's 4000 W, at 690 V it's 5500 W. Horsepower ratings: 1 hp at 230 V, 2 hp at 200/208 V and 220/230 V, 5 hp at 460/480 V and 575/600 V. Current ratings: 7.6 A at 480 V, 6.33 A at 600 V.

MPN