Skip to main content
Siemens 3RA2225-1JD24-0AK6 — Motor Starters

Siemens 3RA2225-1JD24-0AK6 SIRIUS reversing starter, S0

MPN3RA2225-1JD24-0AK6

Siemens SIRIUS 3RA2225-1JD24-0AK6 reversing motor starter, S0 size, CLASS 10, 690 V AC-3, 4 kW at 400 V, 90 x 155 x 260 mm, snap-on 60 mm busbar.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA2225-1JD24-0AK6 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS0
Product design / constructionreversing starter
Circuit-breaker sizeS00
Included contactor (type)3RT2024-1AK60
Included circuit-breaker (type)3RV2011-1JA15
Included link module (type)3RA2921-1AA00

Ratings & Performance

3RA2225-1JD24-0AK6 — Ratings & Performance
ParameterValue
Rated motor power at 400 V4 000 W
Operational current Ie, AC-3 at 400 V8.5 A
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)5 hp
Rated motor power at 575/600 V (hp)7.5 hp
Rated current at 480 V7.92 A
Rated current at 600 V9.19 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)10 000 000

Protection & Tripping

3RA2225-1JD24-0AK6 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)7 ... 10 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2

Contacts & Control

3RA2225-1JD24-0AK6 — Contacts & Control
ParameterValue
Rated value690 V
Rated voltage range at 50 Hz88 ... 121 V
Auxiliary contacts, NO3
Auxiliary contacts, NC3
Auxiliary switch extensionYes
Switching contact typeelectromechanical

Mechanical & Connection

3RA2225-1JD24-0AK6 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (16 ... 12), 2x (14 ... 8)
Mounting / fastening methodfor snapping onto 60 mm busbar systems
Mounting positionvertical
Width90 mm
Height260 mm
Depth155 mm

Environmental

3RA2225-1JD24-0AK6 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

Reversing starter, S0 frame — what ships in the carton

The 3RA2225-1JD24-0AK6 is a SIRIUS non-fused reversing motor starter in size S0, designed for snapping onto 60 mm busbar systems. It ships as a complete assembly: the supplied contactor is 3RT2024-1AK60 and the link module is 3RA2921-1AA00 — no loose parts to chase.

Electrical ratings — AC-3 motor switching at 690 V max

At 400 V the starter is rated for 4 000 W; at 500 V it handles 5 500 W. The control coil accepts 88–121 V at 50 Hz and 96–132 V at 60 Hz — a wide tolerance that handles nominal 110/120 V supplies with margin for brownout.

Mounting dimensions and clearances — panel fit check

Dimensions: 90 mm wide, 155 mm deep, 260 mm tall. Mounting position is vertical only. Clearance requirements: 30 mm upwards, 10 mm forwards, 10 mm downwards, 9 mm at the side, and 0 mm backwards — the back can sit flush against the panel wall. Wire range for main contacts: 1–10 mm² stranded, or 2× (2.5–6 mm²) — suitable for common motor feeder cables up to 10 mm².

Environmental limits and compliance

Pollution degree 3 (conductive pollution, typical for industrial control panels). Substance prohibitance date is 03/01/2017 — the starter complies with RoHS and REACH requirements as of that date.

MPN
3RA2225-1JD24-0AK6