Specifications

3RA2316-8XB30-2AP0 — Identification
ParameterValue
Product designationReversing contactor assembly
Main circuit poles3
BrandSIRIUS
Reference designation (IEC 81346-2)Q
3RA2316-8XB30-2AP0 — Ratings & Performance
ParameterValue
Rated motor power at 400 V4 kW
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)5 hp
Rated motor power at 575/600 V (hp)7.5 hp
Rated current at 480 V7.6 A
Rated current at 600 V9 A
3RA2316-8XB30-2AP0 — Contacts & Control
ParameterValue
Rated voltage range at 50 Hz230 V
Control supply voltage typeAC
Auxiliary switch extensionYes
3RA2316-8XB30-2AP0 — Communication
ParameterValue
AS-Interface protocol supportNo
3RA2316-8XB30-2AP0 — Mechanical & Connection
ParameterValue
Mounting / fastening methodscrew and snap-on mounting onto 35 mm DIN rail
Mounting position+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
Width90 mm
Height84 mm
Depth83 mm
3RA2316-8XB30-2AP0 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C

Product details

Reversing a motor load in a compact panel

The Siemens 3RA2316-8XB30-2AP0 is a SIRIUS reversing contactor assembly — two contactors mechanically interlocked in a single housing, so a forward/reverse motor direction change happens without a separate reversing starter or external wiring of the interlock.

Motor power and current across supply voltages

At 400 V the assembly delivers 4 kW; at 480 V the rated current is 7.6 A; at 600 V it reaches 9 A — covering common North American and IEC motor voltages from 200/208 V (2 hp) up to 575/600 V (7.5 hp). Maximum switching frequency is 750 operations per hour in AC-3 and AC-3e duty — adequate for most motor start/stop cycles but not for high-speed jogging.

Termination and wiring — spring-loaded throughout

Both the main current circuit and the magnet coil use spring-loaded terminals — no screw tightening needed, which cuts wiring time and eliminates vibration loosening on a reversing contactor that cycles frequently.

The assembly ships with two 3RT2016-2AP02 contactors pre-installed and interlocked — the order code covers the complete reversing starter, not a kit.

Frequently asked questions

What is the closest pin-compatible alternative to the 3RA2316-8XB30-2AP0?

The assembly uses two 3RT2016-2AP02 contactors; a functionally equivalent reversing starter would need the same contactor frame size (S00) and coil voltage (230 V 50/60 Hz) to match the panel wiring.

MPN