Skip to main content
Siemens 3RA2325-8XB30-1BB4 — Motor Starters

Siemens SIRIUS 3RA2325-8XB30-1BB4 Reversing Contactor Assemb

MPN3RA2325-8XB30-1BB4
Active

Siemens SIRIUS reversing contactor assembly, S0 size, 7.5 kW at 400 V AC-3, 24 VDC coil, screw-type terminals, DIN rail mount.

$134.62Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RA2325-8XB30-1BB4 — Identification
ParameterValue
Product designationReversing contactor assembly
Main circuit poles3
BrandSIRIUS
Reference designation (IEC 81346-2)Q
3RA2325-8XB30-1BB4 — Ratings & Performance
ParameterValue
Rated motor power at 400 V7.5 kW
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)10 hp
Rated motor power at 575/600 V (hp)15 hp
Rated current at 480 V14 A
Rated current at 600 V17 A
3RA2325-8XB30-1BB4 — Contacts & Control
ParameterValue
Control supply voltage typeDC
Auxiliary switch extensionYes
3RA2325-8XB30-1BB4 — Communication
ParameterValue
AS-Interface protocol supportNo
3RA2325-8XB30-1BB4 — Mechanical & Connection
ParameterValue
Main contact conductor range (AWG)2x (16 ... 12), 2x (14 ... 8)
Mounting / fastening methodscrew and snap-on mounting onto 35 mm standard mounting rail
Mounting position+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
Width90 mm
Height101 mm
Depth107 mm
3RA2325-8XB30-1BB4 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C

Product details

It comes pre-loaded with two 3RT2025-1BB40 contactors, mechanically and electrically interlocked for direction reversal of three-phase motors up to 7.5 kW at 400 V AC-3 duty. The 24 VDC coil is standard, and all main and coil connections use screw-type terminals. Rated for AC-3 and AC-3e switching up to 690 V maximum, this assembly handles motor loads across common global voltages: 7.5 kW at 400 V and 500 V, 11 kW at 690 V, 14 A at 480 V, and 17 A at 600 V. Horsepower equivalents are 5 hp at 230 V, 10 hp at 460/480 V, and 15 hp at 575/600 V.

The S0 footprint measures 90 mm wide, 101 mm tall, and 107 mm deep — a compact envelope for reversing duty. Clearance requirements are 6 mm upward, forward, and to the sides, with zero clearance needed backward. Wire termination for the main circuit accepts solid conductors: 2x (1 to 2.5 mm²) and 2x (2.5 to 10 mm²). Coil and auxiliary wiring uses screw terminals for 2x (0.5 to 1.5 mm²) solid or stranded, and 2x (0.75 to 2.5 mm²).

Shock resistance is 11.8 g / 5 ms and 7.4 g / 10 ms for AC, and 15 g / 5 ms and 10 g / 10 ms for DC. Maximum switching frequency under AC-3 or AC-3e load is 1,000 operations per hour.

Frequently asked questions

What are the key dimensions for panel layout?

Width 90 mm, height 101 mm, depth 107 mm. Requires 6 mm clearance upward, forward, and to the sides; zero clearance needed backward.

What wire sizes does the main circuit accept?

Solid conductors: 2x (1 to 2.5 mm²) and 2x (2.5 to 10 mm²). Coil/auxiliary terminals accept 2x (0.5 to 1.5 mm²) solid or stranded, and 2x (0.75 to 2.5 mm²). All connections are screw-type.

MPN
3RA2325-8XB30-1BB4