The 3RA2328-8XB30-1AG2: No stock-holding claim — quoted per order.
What the 34 A at 480 V rating means for fit
The headline 34 A at 480 V is the AC-3 motor-switching current — the value that governs whether this assembly starts and stops a given motor without welding the contacts. For a 480 V three-phase motor, 34 A in AC-3 translates to roughly 25 hp, which matches the 25 hp rating at 460/480 V on the spec line. At 400 V, the assembly is rated 18.5 kW in AC-3 duty — that is the continuous motor load it handles across the line. The AC-4 rating (inching / plugging duty) at 400 V is 11 kW, about 60 % of the AC-3 figure, so if the application requires frequent reversing under load, size against the AC-4 number, not the AC-3 headline.
Mounting and wiring — drops into a standard S0 panel footprint
S0 contactor size, 90 mm wide, 101 mm tall, 97 mm deep — fits the standard S0 DIN-rail footprint. All terminals are screw-type — no special crimp tooling needed for the panel build.
Mechanical life and environmental limits
Rated for 10,000,000 operating cycles typical — that is the mechanical life of the contactor mechanism, not the electrical life under load. In a reversing application that cycles once every 10 seconds, that is roughly 3 years of continuous 24/7 operation before the mechanism wears out. Shock resistance: 13.5 g / 5 ms and 8.3 g / 10 ms on AC, 15 g / 5 ms and 10 g / 10 ms on DC. The clearance around the assembly: 6 mm upwards, forwards, downwards, and to the side; 0 mm backwards — it can sit flush against the back panel.