Skip to main content
Siemens 3RA2415-8XF31-1BB4 — Motor Starters

Siemens 3RA2415-8XF31-1BB4 SIRIUS Star-Delta Starter

MPN3RA2415-8XF31-1BB4
Active

Siemens SIRIUS 3RA2415-8XF31-1BB4 star-delta (wye-delta) contactor assembly, Size S00, 5.5 kW at 400 V AC-3, 24 VDC coil, screw terminals, 145 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RA2415-8XF31-1BB4 — Identification
ParameterValue
Product designationContactor assembly for star-delta (wye-delta) start
Main circuit poles3
BrandSIRIUS
Reference designation (IEC 81346-2)Q
3RA2415-8XF31-1BB4 — Ratings & Performance
ParameterValue
Rated motor power at 400 V5.5 kW
Rated voltage at AC-3, max.690 V
3RA2415-8XF31-1BB4 — Contacts & Control
ParameterValue
Control supply voltage typeDC
Auxiliary switch extensionNo
3RA2415-8XF31-1BB4 — Communication
ParameterValue
AS-Interface protocol supportNo
3RA2415-8XF31-1BB4 — Mechanical & Connection
ParameterValue
Main contact conductor range (AWG)2x (20 ... 16), 2x (18 ... 14)
Mounting / fastening methodscrew and snap-on mounting onto 35 mm standard mounting rail
Mounting position+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
Width135 mm
Height68 mm
Depth145 mm
3RA2415-8XF31-1BB4 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C

Product details

Star-delta contactor assembly for controlled motor starting

The SIRIUS 3RA2415-8XF31-1BB4 is a factory-assembled star-delta (wye-delta) starter kit containing three 3RT2015-1BB41 contactors and the interlocking RS assembly kit 3RA2913-2BB1. It reduces inrush current during motor start by connecting the windings in star, then switching to delta for full-load running. The 24 VDC coil (screw-type terminals) matches standard control voltage rails in industrial panels.

Mechanical endurance and switching constraints

The assembly withstands shock of 10.5g for 5 ms and 6.6g for 10 ms on both AC and DC supplies — relevant for installations on vibrating machinery or conveyors.

Wiring and terminal capacity for the BOM freeze

Main current circuit and auxiliary/control circuit terminals are screw-type. AWG equivalents: 2x (20 to 16) and 2x (18 to 14). No integrated auxiliary switch or bus communication module is fitted — these are external add-ons if needed. The recommended upstream fuse for type 2 coordination is gG NH 3NA, DIAZED 5SB, or NEOZED 5SE rated at 20 A.

Production status and sourcing posture

Substance prohibition date per RoHS/REACH compliance is noted as 10/01/2009, indicating the design meets EU substance restrictions effective from that date.

Frequently asked questions

What is the 3RA2415-8XF31-1BB4 used for?

It is a Siemens SIRIUS star-delta (wye-delta) contactor assembly for controlled starting of three-phase induction motors, reducing inrush current.

MPN
3RA2415-8XF31-1BB4