Skip to main content
Siemens 3RA2417-8XF31-2BB4-ZX95 — Motor Starters

Siemens 3RA2417-8XF31-2BB4-ZX95 SIRIUS Star-Delta Contactor

MPN3RA2417-8XF31-2BB4-ZX95

Siemens SIRIUS star-delta contactor assembly, 3RA2417-8XF31-2BB4-ZX95, size S00, 11 kW at 400 V AC-3, spring-loaded terminals, supplied with three contactors and RS assembly kit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RA2417-8XF31-2BB4-ZX95 — Identification
ParameterValue
Product designationContactor assembly for star-delta (wye-delta) start
Main circuit poles3
BrandSIRIUS
Reference designation (IEC 81346-2)Q
3RA2417-8XF31-2BB4-ZX95 — Ratings & Performance
ParameterValue
Rated motor power at 400 V11 kW
3RA2417-8XF31-2BB4-ZX95 — Contacts & Control
ParameterValue
Control supply voltage typeDC
Auxiliary switch extensionNo
3RA2417-8XF31-2BB4-ZX95 — Communication
ParameterValue
AS-Interface protocol supportNo
3RA2417-8XF31-2BB4-ZX95 — Mechanical & Connection
ParameterValue
Main contact conductor range (AWG)1x (20 ... 12)
Mounting / fastening methodscrew and snap-on mounting onto 35 mm standard mounting rail
Mounting position+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
Width135 mm
Height84 mm
Depth145 mm
3RA2417-8XF31-2BB4-ZX95 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C

Product details

The Siemens SIRIUS 3RA2417-8XF31-2BB4-ZX95 is a pre-assembled star-delta (wye-delta) contactor assembly for motor starting, rated 11 kW at 400 V, 500 V, and 690 V. It ships with three contactors: two 3RT2018-2BB41 and one 3RT2016-2BB41, plus the 3RA2913-2BB2 RS assembly kit. All power and control connections use spring-loaded terminals — no screw torque to verify, no periodic re-tightening.

Mounts on 35 mm standard DIN rail via screw or snap-on fastening. The size S00 footprint measures 135 mm wide by 84 mm high by 145 mm deep. Clearance requirements: 6 mm upwards, forwards, and to the sides; 0 mm backwards.

Wiring and protection

Power circuit spring terminals accept 2x (0.5 to 4 mm²) solid or 2x (0.5 to 2.5 mm²) stranded; AWG equivalents are 1x (20 to 12). For gG fuse protection, the assembly requires 25 A fuses (type NH 3NA, DIAZED 5SB, or NEOZED 5SE). No auxiliary switch or bus communication module is included — this is a standalone motor-starting assembly.

Frequently asked questions

How do I get current pricing and availability for 3RA2417-8XF31-2BB4-ZX95?

Submit an RFQ through this listing. Pricing and availability are confirmed at quote time through independent distribution channels.

What is 3RA2417-8XF31-2BB4-ZX95's listed depth?

The depth is 145 mm.

What compliance documentation does this brand provide for 3RA2417-8XF31-2BB4-ZX95?

The part is RoHS compliant (substance prohibition date October 1, 2009). Evidence does not list UL, CSA, or IEC certifications — verify with the manufacturer for full documentation.

MPN
3RA2417-8XF31-2BB4-ZX95