Skip to main content
Siemens 3RA2425-8XH32-1BB4 — Motor Starters

Siemens 3RA2425-8XH32-1BB4 SIRIUS Star-Delta Starter

MPN3RA2425-8XH32-1BB4
NRND

Siemens SIRIUS 3RA2425-8XH32-1BB4 contactor assembly for star-delta (wye-delta) motor starting, S0 frame, 15 kW at 400 V, 24 VDC coil, screw-type terminals, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA2425-8XH32-1BB4 — Identification
ParameterValue
Product designationContactor assembly for star-delta (wye-delta) start
Main circuit poles3
BrandSIRIUS
Reference designation (IEC 81346-2)Q

Ratings & Performance

3RA2425-8XH32-1BB4 — Ratings & Performance
ParameterValue
Rated motor power at 400 V15 kW

Contacts & Control

3RA2425-8XH32-1BB4 — Contacts & Control
ParameterValue
Control supply voltage typeDC
Auxiliary switch extensionNo

Communication

3RA2425-8XH32-1BB4 — Communication
ParameterValue
AS-Interface protocol supportYes

Mechanical & Connection

3RA2425-8XH32-1BB4 — Mechanical & Connection
ParameterValue
Main contact conductor range (AWG)2x (16 ... 12), 2x (14 ... 8)
Mounting / fastening methodscrew and snap-on mounting onto 35 mm standard mounting rail
Mounting position+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
Width135 mm
Height101 mm
Depth181 mm

Environmental

3RA2425-8XH32-1BB4 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C

Product details

What this star-delta assembly contains and how it mounts

The 3RA2425-8XH32-1BB4 is a factory-assembled SIRIUS contactor set for star-delta (wye-delta) motor starting — it ships with three contactors: two 3RT2026-1BB40 (one with a -0CC0 suffix) and one 3RT2024-1BB40, plus the RS assembly kit 3RA2923-2BB1. The assembly mounts on 35 mm DIN rail (screw and snap-on) and occupies an S0 frame footprint: 135 mm wide, 101 mm high, 181 mm deep. Clearance requirements around the unit are 6 mm upward, forward, downward, and to the side; no clearance needed at the rear.

Motor power ratings and coil drive

The required upstream fuse for coordination is 35 A (gG NH 3NA, DIAZED 5SB, or NEOZED 5SE types). The magnet coil is 24 VDC with a closing and holding power of 13.8 W — a DC coil means no hum and consistent pull-in force regardless of line frequency, but the DC supply must be capable of delivering the inrush at coil closure. The assembly is rated for vibration at 11.8 g / 5 ms and 7.4 g / 10 ms (AC) and 15 g / 5 ms and 10 g / 10 ms (DC) — figures that matter for applications on mobile equipment or near rotating machinery.

Termination and wiring details

Main current circuit and auxiliary/control circuit both use screw-type terminals. AWG equivalents for main contacts are 2x (16 to 12) and 2x (14 to 8). The assembly has 3 instantaneous main contacts and no built-in auxiliary switch or bus communication — any auxiliary contacts or fieldbus interface must be added externally via the SIRIUS accessory range.

The mechanical life of the contactors is typical 10 million operations — a figure that assumes proper coil drive and contactor application within rated duty. For high-cycle applications (frequent starts per hour), factor in the contactor electrical life at the specific motor current.

Frequently asked questions

What are the motor power ratings for 3RA2425-8XH32-1BB4 at different voltages?

Rated motor power is 15 kW at 400 V, 19 kW at 500 V, and 19 kW at 690 V, all in AC-3 duty. The required upstream fuse for coordination is 35 A (gG NH 3NA, DIAZED 5SB, or NEOZED 5SE types).

MPN
3RA2425-8XH32-1BB4