Skip to main content
Siemens 3RA2712-1CB00 — Motor Starters

Siemens 3RA2712-1CB00 AS-i Basic Module, Star-Delta Starter

MPN3RA2712-1CB00

Siemens Sirius 3RA2712-1CB00 AS-i basic module, star-delta (wye-delta) starter, 24 V DC control supply, screw-type terminals, varistor surge suppression, IP20 finger-safe front, 45 mm width.

$120.65Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RA2712-1CB00 — Identification
ParameterValue
Product designationBasic module
BrandSirius
Product design / constructionAS-i
3RA2712-1CB00 — Ratings & Performance
ParameterValue
Rated insulation voltage Ui (AC, pollution degree 3)690V
3RA2712-1CB00 — Contacts & Control
ParameterValue
Control supply voltage typeDC
3RA2712-1CB00 — Mechanical & Connection
ParameterValue
Mounting / fastening methodcan be plugged into contactor
Mounting positionany
Width45mm
Height37mm
Depth75mm
3RA2712-1CB00 — Environmental
ParameterValue
Operating temperature range-25 ... +60°C
Storage temperature range-40 ... +80°C
Transport temperature range-40 ... +80°C
Pollution degree3

Product details

What this AS-i module does — star-delta starting on the bus

The 3RA2712-1CB00 is a Sirius basic module that adds AS-i bus communication to a star-delta (wye-delta) starter assembly. It plugs onto the front of a communication-capable Siemens contactor (3RT20…-…..-0CC0 series) — no separate DIN rail mount needed. Control supply is 24 V DC, the standard industrial bus voltage. It handles star-delta starting logic over the AS-i network, meaning the transition timing and motor protection can be managed from the PLC rather than a separate timer relay.

Mounting and wiring — fits which contactors, what wire sizes

The module snaps onto the front of contactor frame sizes S00, S0, S2, or S3. That covers the common Siemens contactor range from small auxiliary to 65 A motor switching. Mounting position is any orientation. Screw-type terminals accept solid wire 0.5–4 mm² or two conductors 0.5–2.5 mm². AWG equivalent is 20–14 for two conductors. The terminal block is removable — you can pre-wire the harness and snap it onto the module during panel assembly.

Environmental and EMC — industrial panel conditions

Rated for industrial ambience A per IEC 60947-1 on both emissions (CISPR 11) and immunity. ESD withstand is 8 kV contact per IEC 61000-4-2; radiated field immunity is 10 V/m per IEC 61000-4-3. This means it's qualified for installation near VFDs, welding gear, and switching power supplies without extra shielding. Pollution degree 3 (conductive pollution or dry non-conductive that becomes conductive with condensation) — typical for control panels in industrial floors. Vibration resistance is 11–55 Hz at 0.35 mm displacement; shock resistance is 11 g for 15 ms. The IP20 front protection is finger-safe per IEC 60529, adequate for enclosed panels.

Insulation voltage and altitude — system voltage limits

Maximum installation altitude is 2000 m above sea level without derating.

Frequently asked questions

What contactor sizes does 3RA2712-1CB00 mount on?

The specific contactor order code suffix is -0CC0.

Does 3RA2712-1CB00 support reversing or direct-on-line starting?

No. This module is specifically designed for star-delta (wye-delta) starting only. It is not a direct starter or reversing starter.

MPN
3RA2712-1CB00