Skip to main content
Siemens 3RA2813-1AW10 — Time Delay Relays

Siemens 3RA2813-1AW10 SIRIUS ON-Delay Timer, 3 A

MPN3RA2813-1AW10
Active

Siemens SIRIUS 3RA2813-1AW10 ON-delay timer relay, 3 A maximum, 24-240 V AC/DC control voltage, adjustable time 0.05-100 s, clip-on DIN rail mounting, 45 x 38 x 74 mm.

$36.83Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RA2813-1AW10 — Identification
ParameterValue
Product designationSolid-state time-delay auxiliary switch
3RA2813-1AW10 — Timing
ParameterValue
ON-delayYes
OFF-delayNo
Delayed switching1
At 24 V1 A
Influence of ambient temperature±1 %
3RA2813-1AW10 — Electrical
ParameterValue
Control supply voltage type (AC/DC)AC/DC
At 50 Hz24 ... 240 V
At 60 Hz24 ... 240 V
Rated surge voltage withstand4 kV
Initial value0.85
Full-scale value1.1
3RA2813-1AW10 — Output / Contacts
ParameterValue
At 250 V0.1 A
At 125 V0.2 A
3RA2813-1AW10 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-40 ... +85 °C
Transport temperature range-40 ... +85 °C
Operating humidity range0 ... 95 %
Pollution degree3
Max. installation altitude2 000 m
Shock resistance (IEC 60068-2-27)15g / 11 ms
Vibration resistance (IEC 60068-2-6)10 ... 59 Hz: 0.35 mm, 60 ... 150 Hz: 2g
ESD immunity (IEC 61000-4-2)8 kV
Burst immunity (IEC 61000-4-4)2 kV network connection / 1 kV control connection
3RA2813-1AW10 — Mechanical
ParameterValue
Fastening methodclip-on
Mounting positionany (like contactor)
Removable terminalsYes
Width45 mm
Height38 mm
Depth74 mm
Wire range, solid (AWG)20 ... 14
Wire range, stranded (AWG)20 ... 14
Wire range, finely stranded w/ ferrule (mm²)0.5 ... 2.5 mm²
Clearance, rear0 mm
Clearance, front0 mm
Clearance, sides0 mm
Clearance, top0 mm
Clearance, bottom0 mm

Product details

The 3RA2813-1AW10 is a SIRIUS ON-delay timer relay with a maximum switching current of 3 A — this is the contact rating, not the load current of the motor starter it controls. It switches the control signal to the contactor coil, so the 3 A ceiling covers most 24-240 V AC/DC contactor coils in the SIRIUS family without derating. The adjustable time range spans 0.05 to 100 s, set via a front-panel potentiometer or DIP switch depending on the variant. Recovery time between cycles is 150 ms — the timer resets fast enough for sequential start applications on conveyor or pump banks. The pickup threshold is 85 % of rated voltage, so it drops out cleanly on a sagging line.

DIN-rail footprint and environmental limits

Depth is 74 mm, height 38 mm; mounting position is any, like a contactor, meaning it can be installed horizontally or vertically in a crowded panel. Pollution degree 3 means it tolerates conductive dust and condensation typical of industrial control cabinets not hermetically sealed.

MPN