Skip to main content
Siemens 3RA2814-2AW10 — Motor Starters

Siemens 3RA2814-2AW10 SIRIUS Motor Starter, 3 A

MPN3RA2814-2AW10
Active

Siemens SIRIUS 3RA2814-2AW10 motor starter, 3 A maximum, 24-240 V AC/DC control voltage, adjustable OFF-delay 0.05-100 s, clip-on mounting, 45 mm width, 74 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RA2814-2AW10 — Identification
ParameterValue
Product designationSolid-state time-delay auxiliary switch
BrandSIRIUS
Reference designation (IEC 81346-2)K
3RA2814-2AW10 — Ratings & Performance
ParameterValue
Rated impulse withstand voltage (Uimp)4 kV
3RA2814-2AW10 — Contacts & Control
ParameterValue
Control supply voltage typeAC/DC
3RA2814-2AW10 — Mechanical & Connection
ParameterValue
Mounting / fastening methodclip-on
Mounting positionany (like contactor)
Width45 mm
Height38 mm
Depth74 mm
3RA2814-2AW10 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-40 ... +85 °C
Transport temperature range-40 ... +85 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)15g / 11 ms

Product details

What the 3 A rating and OFF-delay mean for your control circuit

The 3RA2814-2AW10: For motor loads, size the overload relay element to the motor nameplate FLA, which will be below 3 A for this frame. The OFF-delay is adjustable from 0.05 to 100 s and is the only timing function on this unit — there is no ON-delay, no pulse-shaping, and no star-delta circuit. The recovery time between cycles is 150 ms, so the relay resets fast enough for sequential start/stop logic. Control voltage is AC/DC from 24 to 240 V (50/60 Hz), with a pickup threshold of 0.85 × rated voltage. At 24 V DC the control circuit draws 1 A; at 125 V DC it draws 0.2 A; at 250 V DC it draws 0.1 A — use these values to size the control transformer and fuse.

Panel fit and mounting — clip-on, any position

The unit clips onto a DIN rail (fastening method: clip-on) and measures 45 mm wide × 38 mm high × 74 mm deep. It can be mounted in any position, like a contactor, so orientation is not a constraint in a crowded enclosure. Clearance around the device: 0 mm upwards, forwards, backwards, downwards, and at the sides — no mandatory air gap for this unit, but standard panel ventilation rules still apply for the surrounding components. Basic insulation type — suitable for standard industrial environments without reinforced isolation requirements.

Frequently asked questions

What is the OFF-delay range on 3RA2814-2AW10?

The OFF-delay is adjustable from 0.05 to 100 seconds. The unit has no ON-delay, no pulse-shaping, and no star-delta circuit — it is a dedicated OFF-delay timer for the motor starter.

Can 3RA2814-2AW10 be used with 24 V DC control voltage?

Yes, the control voltage range is 24-240 V AC/DC. At 24 V DC the control circuit draws 1 A.

Where can I buy 3RA2814-2AW10?

Submit an RFQ for current availability and pricing — no stock-holding claim is made here.

MPN
3RA2814-2AW10