Compact Starter for Motor Protection and Control
The adjustable Trip Class (10 or 20) lets you match the thermal overload curve to the motor start profile: Class 10 for short acceleration times like pumps, Class 20 for high-inertia loads like fans or conveyors.
Screw-type terminals on the main circuit accept 0.5 to 4 mm² solid or stranded, or 2x 0.5 to 2.5 mm² — typical for motor branch circuits up to 370 W at 400 V. Strip length for screw terminals is standard; no special tooling required. Coil supply is 24 V AC/DC (24 V at 50/60 Hz, 24 V DC), with a 2.8 W AC / 2.9 W DC power draw — compatible with standard 24 V control transformers or power supplies. Two LEDs indicate status.
Vibration resistance up to 20 m/s² at 5.8–500 Hz and shock resistance of 60 m/s² (6g) per 3 shocks in all axes means it holds up on a machine frame or conveyor line. Degree of Pollution 3 (conductive or dry non-conductive pollution) — typical for industrial control panels not in clean-room environments. Any mounting position allowed.