Skip to main content
Siemens 3RA6250-2AP32 — Motor Starters

Siemens 3RA6250-2AP32 SIRIUS Reversing Starter

MPN3RA6250-2AP32
Active

Siemens SIRIUS 3RA6250-2AP32 compact reversing starter, 53 kA at 400 V, adjustable CLASS 10/20, spring-loaded terminals, AC/DC 110-240 V control, 90 mm width, 191 mm height, 165 mm depth.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA6250-2AP32 — Identification
ParameterValue
Product designationcompact starter
Main circuit poles3
BrandSIRIUS
Product design / constructionreversing starter
Reference designation (IEC 81346-2)Q

Ratings & Performance

3RA6250-2AP32 — Ratings & Performance
ParameterValue
Rated motor power at 400 V90 W
Rated current at 480 V0.4 A
Rated current at 600 V0.4 A
Rated impulse withstand voltage (Uimp)6 000 V

Protection & Tripping

3RA6250-2AP32 — Protection & Tripping
ParameterValue
Trip classCLASS 10 and 20 adjustable
Short-circuit protectionYes
Overload release setting range (current)0.1 ... 0.4 A
Duty / utilization type (IEC 60947-6-2)continous operation according to IEC 60947-6-2

Contacts & Control

3RA6250-2AP32 — Contacts & Control
ParameterValue
Rated voltage range at 50 Hz240 V
Auxiliary contacts, NO2
Auxiliary contacts, NC0
Auxiliary switch extensionYes

Mechanical & Connection

3RA6250-2AP32 — Mechanical & Connection
ParameterValue
Main contact conductor range (AWG)2x (16 ... 10), 1x 8
Mounting / fastening methodscrew and snap-on mounting
Mounting positionany
Width90 mm
Height191 mm
Depth165 mm

Environmental

3RA6250-2AP32 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-55 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3

Product details

Reversing starter with adjustable trip class

The Siemens 3RA6250-2AP32 is a SIRIUS compact reversing starter — two contactors in one housing with mechanical interlock, so a single device handles forward/reverse motor control without external interlocks. Trip class is adjustable between CLASS 10 and CLASS 20, which means the same unit can be set for fast protection on a conveyor motor (CLASS 10) or given longer thermal budget for a high-inertia fan start (CLASS 20). Rated for continuous operation per IEC 60947-6-2, so it holds the unit on the grid for sustained duty cycles without derating — not a short-time intermittent device.

SCCR and wire termination that matter for panel build

If your panel SCCR target is 50 kA at 400 V, this starter lands inside the window without a current-limiting device ahead of it. Mounting is screw and snap-on to standard DIN rail; the 90 mm width and 191 mm height fit a standard 200 mm deep enclosure with room for the 165 mm depth plus wiring clearance.

Control voltage flexibility and environmental limits

Coil accepts AC or DC from 110 V to 240 V, 50/60 Hz — one part number covers 120 V and 240 V control systems, and the same coil works on a 125 VDC battery-backed control bus. Operating temperature range is -20 to +60 °C, storage and transport -55 to +80 °C — fine for unheated warehouses and outdoor cabinet installations provided the internal cabinet temperature stays below 60 °C. Vibration resistance tested to 20 m/s² at 5.8-500 Hz and shock rated at 60 m/s² (6g) — survives the mechanical environment of a reversing starter on a vibrating conveyor or compressor skid.

No stock-holding claim — confirmed per RFQ.

Frequently asked questions

What is the 3RA6250-2AP32's short-circuit breaking capacity?

It is rated 53 kA at 400 V. This is the SCCR for the reversing starter itself — the upstream protection device must be coordinated to this level.

What wire sizes does the 3RA6250-2AP32 accept on the main circuit?

No ferrule is required for stranded wire, but the range covers standard control wiring up to 1.5 mm².

MPN