Skip to main content
Siemens 3RA6400-2AB42 — Motor Starters

Siemens 3RA6400-2AB42 SIRIUS Compact Starter, IO-Link

MPN3RA6400-2AB42

Siemens SIRIUS compact starter for IO-Link, direct starter design, 24 V DC, adjustable Class 10/20 trip, 0.09 kW at AC-3 400 V, 53 kA at 400 V.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA6400-2AB42 — Identification
ParameterValue
Product designationCompact starter for IO-Link
Main circuit poles3
BrandSIRIUS
Product design / constructiondirect starter
Reference designation (IEC 81346-2)Q

Ratings & Performance

3RA6400-2AB42 — Ratings & Performance
ParameterValue
Rated motor power at 400 V90 W
Rated current at 480 V0.4 A
Rated current at 600 V0.4 A
Rated impulse withstand voltage (Uimp)6 000 V

Protection & Tripping

3RA6400-2AB42 — Protection & Tripping
ParameterValue
Trip classCLASS 10 and 20 adjustable
Short-circuit protectionYes
Overload release setting range (current)0.1 ... 0.4 A
Duty / utilization type (IEC 60947-6-2)continous operation according to IEC 60947-6-2

Contacts & Control

3RA6400-2AB42 — Contacts & Control
ParameterValue
Auxiliary contacts, NO0
Auxiliary contacts, NC0
Auxiliary switch extensionYes

Mechanical & Connection

3RA6400-2AB42 — Mechanical & Connection
ParameterValue
Mounting / fastening methodscrew and snap-on mounting
Mounting positionany
Width45 mm
Height191 mm
Depth165 mm

Environmental

3RA6400-2AB42 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-55 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3

Product details

The Siemens 3RA6400-2AB42 is a SIRIUS compact starter designed as a direct starter for continuous operation per IEC 60947-6-2. The 24 V DC coil draws a maximum of 2.9 W, and the adjustable trip class (CLASS 10 or 20) lets you match the overload release to the motor start profile — Class 10 for faster starts, Class 20 for higher-inertia loads.

IO-Link and signal integrity

IO-Link is built in at COM2 (38.4 kBaud), so the starter reports load current, trip status, and thermal capacity directly to the controller without a separate analog card. Three LEDs on the front give local status — useful when the line is down and you're walking the panel.

At 45 mm wide × 191 mm high × 165 mm deep, it occupies a single DIN-rail slot. Mounting position is any, but the recommended orientation is vertical on a horizontal DIN rail. The -20 to +60 °C operating range covers most unventilated enclosures, and the pollution degree 3 rating means it tolerates conductive dust and humidity typical of industrial control rooms. Shock and vibration resistance are specified: 6g for 10 ms shocks and 20 m/s² vibration up to 500 Hz — it will hold calibration on a conveyor line or a pump skid.

Frequently asked questions

What is the difference between 3RA6400-2AB42 and 3RA6400-2AB41?

The order code suffix indicates a specific variant within the SIRIUS compact starter family. The 3RA6400-2AB42 is a direct starter with IO-Link, 24 V DC coil, and adjustable Class 10/20 trip. The sibling 3RA6400-2AB41 shares the same form factor and IO-Link but may differ in coil voltage or trip settings — verify the full order code against your BOM.

MPN
3RA6400-2AB42