Skip to main content
Siemens 3RA6400-2CB42 — Motor Starters

Siemens 3RA6400-2CB42 SIRIUS Compact Starter, 4 A, 53 kA

MPN3RA6400-2CB42

Siemens SIRIUS 3RA6400-2CB42 compact direct starter for IO-Link, 4 A at 400 V AC, 53 kA breaking capacity, adjustable CLASS 10/20 trip, spring-loaded terminals, 45 mm wide.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA6400-2CB42 — Identification
ParameterValue
Product designationCompact starter for IO-Link
Main circuit poles3
BrandSIRIUS
Product design / constructiondirect starter
Reference designation (IEC 81346-2)Q

Ratings & Performance

3RA6400-2CB42 — Ratings & Performance
ParameterValue
Rated motor power at 400 V1 500 W
Rated motor power at 460/480 V (hp)2 hp
Rated motor power at 575/600 V (hp)3 hp
Rated current at 480 V4 A
Rated current at 600 V4 A
Rated impulse withstand voltage (Uimp)6 000 V

Protection & Tripping

3RA6400-2CB42 — Protection & Tripping
ParameterValue
Trip classCLASS 10 and 20 adjustable
Short-circuit protectionYes
Overload release setting range (current)1 ... 4 A
Duty / utilization type (IEC 60947-6-2)continous operation according to IEC 60947-6-2

Contacts & Control

3RA6400-2CB42 — Contacts & Control
ParameterValue
Auxiliary contacts, NO0
Auxiliary contacts, NC0
Auxiliary switch extensionYes

Mechanical & Connection

3RA6400-2CB42 — Mechanical & Connection
ParameterValue
Main contact conductor range (AWG)2x (16 ... 10), 1x 8
Mounting / fastening methodscrew and snap-on mounting
Mounting positionany
Width45 mm
Height191 mm
Depth165 mm

Environmental

3RA6400-2CB42 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-55 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3

Product details

Compact starter with IO-Link — 4 A, 53 kA breaking capacity

The 3RA6400-2CB42: The adjustable trip class (CLASS 10 and 20) lets you match the thermal overload curve to the motor start profile: CLASS 10 for short acceleration times like pumps and fans, CLASS 20 for high-inertia loads like conveyors or crushers that need a longer start ramp.

IO-Link integration and terminal wiring

IO-Link protocol is supported at COM2 transfer rate (38.4 kBaud), so the starter communicates process data (current, status, trip diagnostics) back to the IO-Link master without a separate fieldbus coupler — the same M12 cable carries power and data. Three status LEDs on the front give local indication of run, fault, and communication status. Supply voltage is 24 V DC nominal (24... 24 V), with a maximum power consumption of 2.9 W at DC — the control supply can share a standard 24 VDC panel power supply without derating for inrush.

Mounting and environmental ratings

Operating temperature range is -20 to +60 °C, storage and transport -55 to +80 °C — suitable for unheated enclosures in temperate climates. Pollution degree 3 means it tolerates conductive dust and humidity typical of industrial control panels. Shock resistance is 6g (60 m/s²) with 10 ms pulses, 3 shocks per axis; vibration resistance covers 4 to 5.8 Hz at 15 mm amplitude and 5.8 to 500 Hz at 20 m/s² for 10 cycles — meets the mechanical robustness needed for machine-mounted panels on conveyors or presses.

Frequently asked questions

What is the breaking capacity of the 3RA6400-2CB42 at 400 V?

This is the maximum fault current the starter can safely interrupt at that voltage, which covers most industrial 400 V distribution systems without requiring an upstream current-limiting fuse.

MPN