Skip to main content
Siemens 3RA6500-1CB42 — Motor Starters

Siemens 3RA6500-1CB42 SIRIUS Compact Reversing Starter, 4 A

MPN3RA6500-1CB42

Siemens SIRIUS 3RA6500-1CB42 compact reversing starter, 4 A at 400 V AC, 53 kA short-circuit rating, IO-Link COM2, screw terminals, 90 x 170 x 165 mm.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA6500-1CB42 — Identification
ParameterValue
Product designationCompact starter for IO-Link
Main circuit poles3
BrandSIRIUS
Product design / constructionreversing starter
Reference designation (IEC 81346-2)Q

Ratings & Performance

3RA6500-1CB42 — Ratings & Performance
ParameterValue
Rated motor power at 400 V1 500 W
Rated motor power at 460/480 V (hp)2 hp
Rated motor power at 575/600 V (hp)3 hp
Rated current at 480 V4 A
Rated current at 600 V4 A
Rated impulse withstand voltage (Uimp)6 000 V

Protection & Tripping

3RA6500-1CB42 — Protection & Tripping
ParameterValue
Trip classCLASS 10 and 20 adjustable
Short-circuit protectionYes
Overload release setting range (current)1 ... 4 A
Duty / utilization type (IEC 60947-6-2)continous operation according to IEC 60947-6-2

Contacts & Control

3RA6500-1CB42 — Contacts & Control
ParameterValue
Auxiliary contacts, NO0
Auxiliary contacts, NC0
Auxiliary switch extensionYes

Mechanical & Connection

3RA6500-1CB42 — Mechanical & Connection
ParameterValue
Mounting / fastening methodscrew and snap-on mounting
Mounting positionany
Width90 mm
Height170 mm
Depth165 mm

Environmental

3RA6500-1CB42 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-55 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3

Product details

Reversing starter with IO-Link, rated 4 A at 400 V

The 3RA6500-1CB42: This is a SIRIUS compact reversing starter — meaning it integrates a contactor and overload relay for forward/reverse motor control in a single 90 mm wide housing. The IO-Link interface (COM2, 38.4 kBaud) gives the PLC direct access to the starter's status, current draw, trip class setting, and fault history — no separate digital input wiring needed for feedback.

Short-circuit rating and trip class — what they mean for panel coordination

Rated 53 kA at 400 V, this starter can be installed on a supply with up to 53 kA prospective fault current without needing a current-limiting upstream breaker — saves a panel slot and avoids a coordination study for the motor branch. Trip class is adjustable between CLASS 10 and CLASS 20. For a pump or fan starting under load, set it to CLASS 20 to avoid nuisance trips during the longer acceleration ramp; for a light-duty conveyor, CLASS 10 gives faster overload protection.

Mounting and wiring — DIN rail, any orientation, screw terminals

Snap-on mounting to standard 35 mm DIN rail, vertical or horizontal orientation accepted. The housing can also be screw-mounted directly to a backplate. Any mounting position is permitted — no derating needed for side or inverted installation.

Environmental and mechanical endurance

Operates from -20 to +60 °C, stores and ships from -55 to +80 °C. Pollution degree 3 (conductive pollution, typical in industrial enclosures without climate control). Shock rated at 60 m/s² (6 g) for 10 ms, three shocks per axis; vibration tested to 20 m/s² up to 500 Hz. No-load switching frequency is 3,600 cycles per hour — adequate for frequent reversing applications like indexing conveyors or shuttle tables.

Frequently asked questions

What is the short-circuit current rating (SCCR) of the 3RA6500-1CB42?

It is rated 53 kA at 400 V. This means it can be installed on a supply with up to 53 kA prospective fault current without requiring a current-limiting upstream device, simplifying panel coordination.

MPN