Skip to main content
Siemens 3RB2056-2FC2-ZX95 — Overload Relays

Siemens 3RB2056-2FC2-ZX95 SIRIUS Solid-State Overload Relay,

MPN3RB2056-2FC2-ZX95

Siemens SIRIUS solid-state overload relay, 3RB2056-2FC2-ZX95, CLASS 20E, 200 A operational current, S6 size, for contactor mounting or stand-alone installation.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RB2056-2FC2-ZX95 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationsolid-state overload relay
Frame size (overload relay)S6
Combinable contactor sizesS6
Reference code (IEC 81346-2)F
3RB2056-2FC2-ZX95 — Protection & Trip
ParameterValue
Overload current setting range50 ... 200 A
Trip classCLASS 20E
Overload release typeelectronic
3RB2056-2FC2-ZX95 — Electrical (main circuit)
ParameterValue
Rated operational current200 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)1 000 V
Rated value (AC-3e), max.1 000 V
Rated surge withstand voltage8 kV
Main current circuitbusbar connection
3RB2056-2FC2-ZX95 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A
Switching current at 24 V2 A
Switching current at 60 V0.55 A
Switching current at 110 V0.3 A
Switching current at 120 V4 A
Switching current at 125 V0.3 A
Switching current at 220 V0.11 A
Switching current at 230 V3 A
3RB2056-2FC2-ZX95 — Connection & Mounting
ParameterValue
Mounting / fastening methodContactor mounting/stand-alone installation
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typescrew-type terminals
Removable aux./control terminalYes
Conductor cross-section: solid1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
Conductor cross-section: solid or stranded1x (0,5 ... 4 mm²), 2x (0,5 ... 2,5 mm²)
Conductor cross-section: finely stranded with ferrule1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
3RB2056-2FC2-ZX95 — Environmental
ParameterValue
Operating temperature-25 ... +60 °C
Storage temperature-40 ... +80 °C
Transport temperature-40 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m
Shock resistance15g / 11 ms
3RB2056-2FC2-ZX95 — Mechanical
ParameterValue
Width120 mm
Height119 mm
Depth155 mm

Product details

Solid-state overload relay for motor protection

The Siemens SIRIUS 3RB2056-2FC2-ZX95 is a solid-state overload relay sized S6, rated for 200 A operational current at AC-3e duty up to 1000 V. The CLASS 20E trip class means it allows a 20-second cold start at 7.2× rated current — the standard for standard-duty motor starting where the load accelerates within that window. It provides electronic overload protection with an integrated auxiliary switch that outputs a "tripped" message on fault, giving the control system a clean status signal without needing a separate contact block. Mounting is flexible: it fastens directly to a contactor or stands alone on the panel plate. The main circuit connects via M8 busbar connections, and the control wiring accepts 1x (0.5–4 mm²) or 2x (0.5–2.5 mm²) solid or stranded wire. The auxiliary contact ratings cover common control voltages: 2 A at 24 V, 4 A at 120 V, 3 A at 230 V, so it drives a PLC input or relay coil directly.

Temperature compensation is active across the operating range. Shock resistance is 15g / 11 ms per IEC 60068-2-27; vibration resistance is 1–6 Hz at 15 mm, 6–500 Hz at 20 m/s² for 10 cycles. The substance prohibition date of 07/01/2006 aligns with RoHS compliance — the part was designed to meet the EU RoHS directive from that date forward.

Frequently asked questions

What does the CLASS 20E trip class mean for motor protection?

CLASS 20E means the relay allows a 20-second cold start at 7.2× the set current before tripping — the standard for normal-duty motor starting where the load accelerates within that window. It matches the trip curve of most general-purpose induction motors.

What is the "tripped" message output on this relay?

The integrated auxiliary switch outputs a dedicated "tripped" message when the relay activates on overload — a clean status signal to the PLC or annunciator without needing a separate auxiliary contact block.

How do I get current pricing and availability for the 3RB2056-2FC2-ZX95?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current pricing and availability — both are confirmed at quote time.

What compliance documentation does the 3RB2056-2FC2-ZX95 carry?

The substance prohibition date of 07/01/2006 aligns with RoHS compliance. The relay is designed to meet the EU RoHS directive from that date. Additional documentation (IEC, UL) is available on request as part of the RFQ process.

MPN
3RB2056-2FC2-ZX95