3RB2066-1MF2 - Siemens

MPN3RB2066-1MF2
Active

Overload relay 160...630 A for motor protection Size S10/S12, Class 10E Contactor mounting/stand-alone installation Main circuit: busbar connection Auxiliary circuit: Spring-type terminal Manual-Automatic-Reset

$251.46Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RB2066-1MF2 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationsolid-state overload relay
Frame size (overload relay)S10, S12
Combinable contactor sizesS10, S12
Reference code (IEC 81346-2)F
3RB2066-1MF2 — Protection & Trip
ParameterValue
Overload current setting range160 ... 630 A
Trip classCLASS 10E
Overload release typeelectronic
3RB2066-1MF2 — Electrical (main circuit)
ParameterValue
Rated operational current630 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)1 000 V
Rated value (AC-3e), max.1 000 V
Rated surge withstand voltage8 kV
Main current circuitbusbar connection
3RB2066-1MF2 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A
Switching current at 24 V2 A
Switching current at 60 V0.55 A
Switching current at 110 V0.3 A
Switching current at 120 V4 A
Switching current at 125 V0.3 A
Switching current at 220 V0.11 A
Switching current at 230 V3 A
3RB2066-1MF2 — Connection & Mounting
ParameterValue
Mounting / fastening methodContactor mounting/stand-alone installation
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typespring-loaded terminals
Removable aux./control terminalYes
Conductor cross-section: solid2x (0.25 ... 1.5 mm²)
Conductor cross-section: solid or stranded2x (0,25 ... 1,5 mm²)
Conductor cross-section: finely stranded with ferrule2x (0.25 ... 1.5 mm²)
3RB2066-1MF2 — Environmental
ParameterValue
Operating temperature-25 ... +60 °C
Storage temperature-40 ... +80 °C
Transport temperature-40 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m
Shock resistance15g / 11 ms
3RB2066-1MF2 — Mechanical
ParameterValue
Width120 mm
Height119 mm
Depth155 mm
MPN