Siemens 3RB3016-1NB0-ZX95 — Overload Relays

Siemens 3RB3016-1NB0-ZX95 SIRIUS solid-state overload relay,

MPN3RB3016-1NB0-ZX95
Active

Siemens SIRIUS solid-state overload relay, size S00, 1.25 A rated thermal current, Trip Class 10E, electronic release, contactor mounting, 45 x 79 x 73 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RB3016-1NB0-ZX95 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationsolid-state overload relay
Frame size (overload relay)S00
Combinable contactor sizesS00
Reference code (IEC 81346-2)F
3RB3016-1NB0-ZX95 — Protection & Trip
ParameterValue
Overload current setting range0.32 ... 1.25 A
Trip classCLASS 10E
Overload release typeelectronic
3RB3016-1NB0-ZX95 — Electrical (main circuit)
ParameterValue
Rated operational current1.25 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated value (AC-3e), max.690 V
Rated surge withstand voltage6 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)0.1 W
Per pole0.03 W
3RB3016-1NB0-ZX95 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A
Switching current at 24 V2 A
Switching current at 60 V0.55 A
Switching current at 110 V0.3 A
Switching current at 120 V4 A
Switching current at 125 V0.3 A
Switching current at 220 V0.11 A
Switching current at 230 V3 A
3RB3016-1NB0-ZX95 — Connection & Mounting
ParameterValue
Mounting / fastening methodContactor mounting
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typescrew-type terminals
Removable aux./control terminalYes
Conductor cross-section: solid1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
Conductor cross-section: solid or stranded1x (0,5 ... 4 mm²), 2x (0,5 ... 2,5 mm²)
Conductor cross-section: finely stranded with ferrule1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
3RB3016-1NB0-ZX95 — Environmental
ParameterValue
Operating temperature-25 ... +60 °C
Storage temperature-40 ... +80 °C
Transport temperature-40 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m
Shock resistance15g / 11 ms
3RB3016-1NB0-ZX95 — Mechanical
ParameterValue
Width45 mm
Height79 mm
Depth73 mm

Product details

The Siemens 3RB3016-1NB0-ZX95 is a SIRIUS solid-state overload relay in the S00 frame size, rated for a thermal current of 1.25 A at up to 690 V. It's an electronic overload release with Trip Class 10E.

The auxiliary contact ratings cover a wide control-voltage range: 2 A at 24 V, 4 A at 120 V, 3 A at 230 V, and 0.55 A at 60 V — so it can switch PLC inputs, contactor coils, or indicator lamps across common control voltages without an interposing relay. The integrated auxiliary switch (design of the auxiliary switch: integrated) means you don't need a separate add-on block for the N/C trip signal.

Integration notes

Wiring the main circuit uses screw-type terminals accepting 1x (0.5 to 4 mm²) or 2x (0.5 to 2.5 mm²) solid or stranded copper. The screwdriver spec calls for a Pozidriv PZ2 tip with a shaft diameter of 5 to 6 mm. Mounting position is any orientation, and the relay withstands 15g / 11 ms shock (signaling contact 9g / 11 ms in tripped position) and vibration per IEC 60068-2-27. The note on the part reads "for message 'tripped'" — that's the auxiliary contact's label, not a fault code.

Frequently asked questions

What does the note 'for message tripped' mean?

That's the label for the integrated auxiliary signaling contact — it closes when the overload relay trips, providing a dry-contact signal to a PLC input or alarm circuit.

Does this relay mount on a DIN rail?

No, it uses contactor mounting — it fastens directly to the front of a matching S00 contactor, not on a DIN rail.