Skip to main content
Siemens 3RB3016-1PB0-ZW96 — Overload Relays

Siemens 3RB3016-1PB0-ZW96 SIRIUS solid-state overload relay

MPN3RB3016-1PB0-ZW96
Active

Siemens SIRIUS 3RB3016-1PB0-ZW96 solid-state overload relay, CLASS 10E, 4 A thermal current, 690 V rated value, S00 frame, contactor mounting, screw-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RB3016-1PB0-ZW96 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationsolid-state overload relay
Frame size (overload relay)S00
Combinable contactor sizesS00
Reference code (IEC 81346-2)F
3RB3016-1PB0-ZW96 — Protection & Trip
ParameterValue
Overload current setting range1 ... 4 A
Trip classCLASS 10E
Overload release typeelectronic
3RB3016-1PB0-ZW96 — Electrical (main circuit)
ParameterValue
Rated operational current4 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated value (AC-3e), max.690 V
Rated surge withstand voltage6 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)0.1 W
Per pole0.03 W
3RB3016-1PB0-ZW96 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A
Switching current at 24 V2 A
Switching current at 60 V0.55 A
Switching current at 110 V0.3 A
Switching current at 120 V4 A
Switching current at 125 V0.3 A
Switching current at 220 V0.11 A
Switching current at 230 V3 A
3RB3016-1PB0-ZW96 — Connection & Mounting
ParameterValue
Mounting / fastening methodContactor mounting
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typescrew-type terminals
Removable aux./control terminalYes
Conductor cross-section: solid1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
Conductor cross-section: solid or stranded1x (0,5 ... 4 mm²), 2x (0,5 ... 2,5 mm²)
Conductor cross-section: finely stranded with ferrule1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
3RB3016-1PB0-ZW96 — Environmental
ParameterValue
Operating temperature-25 ... +60 °C
Storage temperature-40 ... +80 °C
Transport temperature-40 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m
Shock resistance15g / 11 ms
3RB3016-1PB0-ZW96 — Mechanical
ParameterValue
Width45 mm
Height79 mm
Depth73 mm

Product details

S00 frame solid-state overload relay, contactor-mounted

The Siemens 3RB3016-1PB0-ZW96 is a SIRIUS solid-state overload relay in the S00 frame size, designed for direct mounting onto a contactor — no separate DIN-rail footprint needed. Rated thermal current is 4 A continuous, with a maximum operating voltage of 690 V (AC-3e rated value). The trip class is CLASS 10E, meaning it will trip within 10 seconds at 7.2× the set current — fast enough to protect standard squirrel-cage motors during a locked-rotor event.

Auxiliary contact ratings and wiring

The integrated auxiliary switch (signaling contact 97/98) is rated for switching at multiple control voltages: 2 A at 24 V, 4 A at 120 V, 3 A at 230 V, and 0.55 A at 60 V — covering most PLC input and relay coil circuits in a panel. Terminals accept 1x (0.5 to 4 mm²) or 2x (0.5 to 2.5 mm²) solid or stranded wire, with screw-type connections requiring a Pozidriv PZ2 tip. The relay measures 45 mm wide × 79 mm high × 73 mm deep — fits the S00 contactor footprint without crowding adjacent devices.

Environmental and mechanical endurance

Operating temperature range is -25 to +60 °C with temperature compensation active across that band — no derating needed for ambient heat up to 60 °C. Storage and transport range extends from -40 to +80 °C. Rated shock resistance is 15g / 11 ms per IEC 60068-2-27 (signaling contact in tripped position: 9g / 11 ms). Vibration resistance covers 1–6 Hz at 15 mm amplitude and 6–500 Hz at 20 m/s² for 10 cycles — suitable for machine-mounted applications with moderate vibration.

Lifecycle and sourcing

Substance prohibitance date is 10/01/2009, indicating RoHS compliance per the manufacturer's declaration.

Frequently asked questions

What does the note 'for message tripped' mean on the 3RB3016-1PB0-ZW96?

The note indicates the signaling contact (terminals 97/98) changes state specifically when the overload relay has tripped — it is not a general status or pre-alarm output. The contact rating under tripped condition is derated to 9g / 11 ms shock resistance vs 15g for the main contacts.

MPN
3RB3016-1PB0-ZW96