Skip to main content
Siemens 3RB3016-1PB0-ZX95 — Overload Relays

Siemens 3RB3016-1PB0-ZX95 SIRIUS solid-state overload relay,

MPN3RB3016-1PB0-ZX95
Active

Siemens SIRIUS 3RB3016-1PB0-ZX95 solid-state overload relay, size S00, Trip Class 10E, 4 A thermal current, 690 V rated, electronic release, contactor mounting.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RB3016-1PB0-ZX95 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationsolid-state overload relay
Frame size (overload relay)S00
Combinable contactor sizesS00
Reference code (IEC 81346-2)F
3RB3016-1PB0-ZX95 — Protection & Trip
ParameterValue
Overload current setting range1 ... 4 A
Trip classCLASS 10E
Overload release typeelectronic
3RB3016-1PB0-ZX95 — Electrical (main circuit)
ParameterValue
Rated operational current4 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated value (AC-3e), max.690 V
Rated surge withstand voltage6 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)0.1 W
Per pole0.03 W
3RB3016-1PB0-ZX95 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A
Switching current at 24 V2 A
Switching current at 60 V0.55 A
Switching current at 110 V0.3 A
Switching current at 120 V4 A
Switching current at 125 V0.3 A
Switching current at 220 V0.11 A
Switching current at 230 V3 A
3RB3016-1PB0-ZX95 — Connection & Mounting
ParameterValue
Mounting / fastening methodContactor mounting
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typescrew-type terminals
Removable aux./control terminalYes
Conductor cross-section: solid1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
Conductor cross-section: solid or stranded1x (0,5 ... 4 mm²), 2x (0,5 ... 2,5 mm²)
Conductor cross-section: finely stranded with ferrule1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
3RB3016-1PB0-ZX95 — Environmental
ParameterValue
Operating temperature-25 ... +60 °C
Storage temperature-40 ... +80 °C
Transport temperature-40 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m
Shock resistance15g / 11 ms
3RB3016-1PB0-ZX95 — Mechanical
ParameterValue
Width45 mm
Height79 mm
Depth73 mm

Product details

The Siemens 3RB3016-1PB0-ZX95 is a SIRIUS solid-state overload relay in size S00, designed to protect motors against overload and phase failure. The relay mounts directly onto a contactor (fastening method: contactor mounting), saving DIN-rail space in the panel. Rated for 690 V and carrying a thermal current of 4 A, this relay handles the control and signaling side of motor circuits in the S00 frame class — think small conveyors, pumps, and fans up to about 1.5 kW at 400 V. The auxiliary switch is integrated, and the relay provides a dedicated "tripped" message signal (Note: for message "tripped"), which can be wired directly into a PLC input or annunciator panel for remote fault indication.

Size S00 means a compact footprint: 45 mm wide, 79 mm high, 73 mm deep. It fastens directly onto the contactor — no separate DIN-rail base needed, which simplifies panel layout and reduces wiring distance to the power stack. Screw-type terminals on the main circuit accept 1× (0.5 to 4 mm²) or 2× (0.5 to 2.5 mm²) solid or stranded wire; use a Pozidriv PZ2 screwdriver with a 5–6 mm diameter shaft. Mounting position is any, so horizontal or vertical panel orientation works. The signaling contact (97/98) carries 2 A at 24 V, 4 A at 120 V, and 3 A at 230 V — enough to drive a small relay or PLC input directly. Vibration resistance is 1–6 Hz at 15 mm amplitude and 6–500 Hz at 20 m/s² for 10 cycles; shock resistance is 15g for 11 ms. That holds up on a contactor mounted inside a panel on a machine frame.

Frequently asked questions

What does the "tripped" message signal on the 3RB3016-1PB0-ZX95 mean?

The relay provides a dedicated signaling contact that changes state when the overload trips, labeled "for message 'tripped'." It can be wired to a PLC input or indicator lamp to give remote fault indication.

What are the key ratings of the 3RB3016-1PB0-ZX95?

It is a solid-state overload relay, size S00, Trip Class 10E, with a thermal current of 4 A and rated voltage of 690 V. The signaling contact handles 2 A at 24 V, 4 A at 120 V, and 3 A at 230 V.

Where can I buy the 3RB3016-1PB0-ZX95?

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

MPN
3RB3016-1PB0-ZX95