Siemens 3RB3026-1QB0-ZW96 — Overload Relays

Siemens 3RB3026-1QB0-ZW96 SIRIUS solid-state overload relay

MPN3RB3026-1QB0-ZW96
Active

Siemens SIRIUS 3RB3026-1QB0-ZW96 solid-state overload relay, S0 size, 25 A thermal current, Class 10E trip, 690 V rated, screw-type terminals, contactor mounting.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RB3026-1QB0-ZW96 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationsolid-state overload relay
Frame size (overload relay)S0
Combinable contactor sizesS0
Reference code (IEC 81346-2)F
3RB3026-1QB0-ZW96 — Protection & Trip
ParameterValue
Overload current setting range6 ... 25 A
Trip classCLASS 10E
Overload release typeelectronic
3RB3026-1QB0-ZW96 — Electrical (main circuit)
ParameterValue
Rated operational current25 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated value (AC-3e), max.690 V
Rated surge withstand voltage6 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)1.2 W
Per pole0.4 W
3RB3026-1QB0-ZW96 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A
Switching current at 24 V2 A
Switching current at 60 V0.55 A
Switching current at 110 V0.3 A
Switching current at 120 V4 A
Switching current at 125 V0.3 A
Switching current at 220 V0.11 A
Switching current at 230 V3 A
3RB3026-1QB0-ZW96 — Connection & Mounting
ParameterValue
Mounting / fastening methodContactor mounting
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typescrew-type terminals
Removable aux./control terminalYes
Conductor cross-section: solid1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
Conductor cross-section: solid or stranded1x (0,5 ... 4 mm²), 2x (0,5 ... 2,5 mm²)
Conductor cross-section: finely stranded with ferrule1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
3RB3026-1QB0-ZW96 — Environmental
ParameterValue
Operating temperature-25 ... +60 °C
Storage temperature-40 ... +80 °C
Transport temperature-40 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m
Shock resistance15g / 11 ms
3RB3026-1QB0-ZW96 — Mechanical
ParameterValue
Width45 mm
Height87 mm
Depth84 mm

Product details

Solid-state overload relay for motor protection

The 3RB3026-1QB0-ZW96 is a SIRIUS solid-state overload relay, S0 frame size, rated for a continuous thermal current of 25 A at 690 V — the same current limit applies at 480 V and 600 V, so it covers standard 400 V and 480 V motor circuits without derating. Trip class is CLASS 10E, meaning it will trip within 10 seconds at a locked-rotor current of 7.2× the set current — a standard match for IEC motor starting duty where the thermal model must protect the winding without nuisance tripping during start. The auxiliary contact set is rated for switching at multiple control voltages: 2 A at 24 V, 4 A at 120 V, 3 A at 230 V, and 0.11 A at 220 V — these cover the common control supply rails in North American and European panels.

Mounting and panel fit

Mounts directly onto the contactor via the fastening method — no separate DIN-rail clip needed. The S0 footprint is 45 mm wide, 87 mm high, 84 mm deep, and the mounting position is any orientation, which simplifies layout in crowded enclosures. Main circuit terminals accept screw-type connections: solid wire 1x (0.5–4 mm²) or 2x (0.5–2.5 mm²), and stranded up to 2x 10 mm². The screwdriver spec calls for Pozidriv PZ2 with a 5–6 mm shaft diameter — standard electrician's tooling.

Environmental and compliance

Operates from -25 to +60 °C with temperature compensation across that range, and survives storage and transport from -40 to +80 °C. Vibration resistance: 1–6 Hz at 15 mm amplitude, 6–500 Hz at 20 m/s² for 10 cycles; shock rated at 15g / 11 ms per IEC 60068-2-27. The substance prohibitance date is 10/01/2009 — this is a RoHS compliance marker (the date after which new equipment placed on the EU market must meet RoHS substance limits). No UL or CSA listing appears in the record; confirm site-specific approval requirements at RFQ.

Frequently asked questions

What does the note 'for message tripped' mean on this relay?

The note indicates that the auxiliary contact set (terminals 97/98) changes state to signal a 'tripped' condition — it is a normally-open contact that closes when the overload relay has operated, providing a remote fault indication to a PLC or annunciator.

What is the depth of the 3RB3026-1QB0-ZW96?

The depth is 84 mm, measured from the mounting face to the farthest projection — this fits within the standard S0 contactor depth envelope.

MPN