Its CLASS 20E trip curve means it allows motor starting inrush up to 20 seconds before tripping — sized for standard induction motors driving pumps, fans, or conveyors where the start is not prolonged. The 4 A thermal current at 690 V rated value sets the continuous load capacity of the relay's main circuit. Contactor mounting means it snaps directly onto a matching SIRIUS contactor, saving DIN-rail space and simplifying the motor starter stack.
Integration notes
Mounts directly on a SIRIUS contactor — no DIN-rail bracket needed. Screw-type terminals accept solid or stranded wire: 1x (0.5 to 4 mm²) or 2x (0.5 to 2.5 mm²) for the main circuit, and 2x 10 mm² stranded for the auxiliary. Vibration resistance 1-6 Hz at 15 mm, 6-500 Hz at 20 m/s², 10 cycles. Shock resistance 15g / 11 ms. The integrated auxiliary switch signals the tripped state — the note for message "tripped" is the relay's own diagnostic output.