Skip to main content
Siemens 3RB3036-2UW1 — Overload Relays

Siemens 3RB3036-2UW1 SIRIUS Solid-State Overload Relay

MPN3RB3036-2UW1
Active

Siemens SIRIUS solid-state overload relay, order code 3RB3036-2UW1, Class 20E, 50 A thermal current, 690 V rated voltage, S2 size.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RB3036-2UW1 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationsolid-state overload relay
Frame size (overload relay)S2
Combinable contactor sizesS2
Reference code (IEC 81346-2)F
3RB3036-2UW1 — Protection & Trip
ParameterValue
Overload current setting range12.5 ... 50 A
Trip classCLASS 20E
Overload release typeelectronic
3RB3036-2UW1 — Electrical (main circuit)
ParameterValue
Rated operational current50 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated value (AC-3e), max.690 V
Rated surge withstand voltage6 kV
Main current circuitstraight-through transformers
Power loss at rated current (hot)0.1 W
Per pole0.03 W
3RB3036-2UW1 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A
Switching current at 24 V2 A
Switching current at 60 V0.55 A
Switching current at 110 V0.3 A
Switching current at 120 V4 A
Switching current at 125 V0.3 A
Switching current at 220 V0.11 A
Switching current at 230 V3 A
3RB3036-2UW1 — Connection & Mounting
ParameterValue
Mounting / fastening methodstand-alone installation
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typescrew-type terminals
Removable aux./control terminalYes
Conductor cross-section: solid1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
Conductor cross-section: solid or stranded1x (0,5 ... 4 mm²), 2x (0,5 ... 2,5 mm²)
Conductor cross-section: finely stranded with ferrule1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
3RB3036-2UW1 — Environmental
ParameterValue
Operating temperature-25 ... +60 °C
Storage temperature-40 ... +80 °C
Transport temperature-40 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m
Shock resistance15g / 11 ms
3RB3036-2UW1 — Mechanical
ParameterValue
Width55 mm
Height81 mm
Depth109 mm

Product details

The 3RB3036-2UW1: The thermal current rating of 50 A holds at both 480 V and 600 V, so it covers the common North American motor voltages without derating. The auxiliary signaling contact is integrated and rated for 2 A at 24 V, 4 A at 120 V, and 3 A at 230 V — enough to drive a PLC input or a contactor coil directly.

The relay mounts stand-alone (no DIN-rail adapter required) and accepts any mounting position. At 55 mm wide, 81 mm tall, and 109 mm deep, it fits into a standard panel footprint without crowding adjacent components.

Terminals accept 1× (0.5 to 4 mm²) or 2× (0.5 to 2.5 mm²) solid or stranded copper. The screwdriver specification calls for a Pozidriv PZ2 tip with a shaft diameter of 5 to 6 mm — a standard electrician's Pozidriv driver, not a slotted or Phillips bit. The note for message 'tripped' indicates that the signaling contact 97/98 changes state when the relay trips, giving a dry-contact indication to the control system.

Frequently asked questions

What is the trip class of 3RB3036-2UW1?

The trip class is CLASS 20E, meaning it allows a 20-second overload at 7.2× rated current before tripping — standard for general-purpose motor starting.

What is the current rating of 3RB3036-2UW1?

The thermal current rating is 50 A, and it holds at both 480 V and 600 V without derating.

Where can I buy 3RB3036-2UW1 and get pricing?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm current pricing and availability.

What does the note 'for message tripped' mean on 3RB3036-2UW1?

It indicates that the signaling contact 97/98 changes state when the relay trips, providing a dry-contact indication to the control system.

MPN
3RB3036-2UW1