Skip to main content
Siemens 3RB3133-4WW1 — Overload Relays

Siemens 3RB3133-4WW1 SIRIUS solid-state overload relay, S2,

MPN3RB3133-4WW1
Active

Siemens SIRIUS solid-state overload relay, size S2, 80 A rated operational current, adjustable trip classes 5E–30E, 55 mm width, 109 mm depth, for message "tripped" signaling.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RB3133-4WW1 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationsolid-state overload relay
Frame size (overload relay)S2
Combinable contactor sizesS2
Reference code (IEC 81346-2)F
3RB3133-4WW1 — Protection & Trip
ParameterValue
Overload current setting range20 ... 80 A
Trip classCLASS 5E, 10E, 20E and 30E adjustable
Overload release typeelectronic
3RB3133-4WW1 — Electrical (main circuit)
ParameterValue
Rated operational current80 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)690 V
Rated value (AC-3e), max.690 V
Rated surge withstand voltage6 kV
Main current circuitstraight-through transformers
Power loss at rated current (hot)0.2 W
Per pole0.07 W
3RB3133-4WW1 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A
Switching current at 24 V2 A
Switching current at 60 V0.55 A
Switching current at 110 V0.3 A
Switching current at 120 V4 A
Switching current at 125 V0.3 A
Switching current at 220 V0.11 A
Switching current at 230 V3 A
3RB3133-4WW1 — Connection & Mounting
ParameterValue
Mounting / fastening methodstand-alone installation
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typescrew-type terminals
Removable aux./control terminalYes
Conductor cross-section: solid1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
Conductor cross-section: solid or stranded1x (0,5 ... 4 mm²), 2x (0,5 ... 2,5 mm²)
Conductor cross-section: finely stranded with ferrule1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
3RB3133-4WW1 — Environmental
ParameterValue
Operating temperature-25 ... +60 °C
Storage temperature-40 ... +80 °C
Transport temperature-40 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m
Shock resistance15g / 11 ms
3RB3133-4WW1 — Mechanical
ParameterValue
Width55 mm
Height81 mm
Depth109 mm

Product details

The Siemens 3RB3133-4WW1 is a SIRIUS solid-state overload relay in size S2, rated for a continuous thermal current of 80 A. It protects motor circuits by monitoring current through straight-through transformers and signaling a "tripped" message when the motor current exceeds the upper setting value by a factor of 3.5, or when it drops below the lower setting.

Designed for stand-alone installation in any mounting position. Shock resistance is rated at 15g for 11 ms (signaling contact drops to 8g / 11 ms in the tripped position). Vibration resistance covers 1–6 Hz at 15 mm amplitude and 6–500 Hz at 20 m/s² over 10 cycles.

Solid or stranded conductors: accepts 1x (0.5–4 mm²) or 2x (0.5–2.5 mm²) per terminal. Screwdriver requirement is Pozidriv PZ2 with a shaft diameter of 5 to 6 mm. The auxiliary switch is integrated, with contact ratings specified at multiple control voltages: 2 A at 24 V, 4 A at 120 V, 3 A at 230 V, and 0.3 A at 125 V. Power dissipation per pole is 0.07 W.

Compliance and substance restrictions

The part carries a substance prohibitance date of October 15, 2014, indicating compliance with RoHS and REACH substance restrictions as of that date.

Frequently asked questions

What is the 3RB3133-4WW1's note for message "tripped"?

The relay signals a "tripped" message when the motor current exceeds the upper current setting value by a factor of 3.5 or drops below the lower current setting value.

What is the physical size of the 3RB3133-4WW1?

Width is 55 mm, height is 81 mm, and depth is 109 mm. It is designed for stand-alone installation in any mounting position.

What compliance documentation does Siemens provide for the 3RB3133-4WW1?

The part carries a substance prohibitance date of October 15, 2014, indicating compliance with RoHS and REACH substance restrictions as of that date.

MPN
3RB3133-4WW1