Skip to main content
Siemens 3RB3143-4XB0 — Overload Relays

Siemens 3RB3143-4XB0 SIRIUS Solid-State Overload Relay

MPN3RB3143-4XB0
Active

Siemens SIRIUS 3RB3143-4XB0 solid-state overload relay, S3 size, 115 A rated thermal current, adjustable trip classes 5E/10E/20E/30E, 70 x 106 x 124 mm, contactor-mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RB3143-4XB0 — Identification
ParameterValue
Product brand nameSIRIUS
Product designationsolid-state overload relay
Frame size (overload relay)S3
Combinable contactor sizesS3
Reference code (IEC 81346-2)F
3RB3143-4XB0 — Protection & Trip
ParameterValue
Overload current setting range32 ... 115 A
Trip classCLASS 5E, 10E, 20E and 30E adjustable
Overload release typeelectronic
3RB3143-4XB0 — Electrical (main circuit)
ParameterValue
Rated operational current115 A
Poles (main circuit)3
Rated operating frequency50 ... 60 Hz
Rated insulation voltage (AC, pollution degree 3)1 000 V
Rated value (AC-3e), max.1 000 V
Rated surge withstand voltage8 kV
Main current circuitscrew-type terminals
Power loss at rated current (hot)4.6 W
Per pole1.53 W
3RB3143-4XB0 — Auxiliary contacts
ParameterValue
Auxiliary contacts: NO1
Auxiliary contacts: NC1
Auxiliary contacts: CO (changeover)0
Auxiliary switch short-circuit protection (required fuse)fuse gG: 6 A
Switching current at 24 V2 A
Switching current at 60 V0.55 A
Switching current at 110 V0.3 A
Switching current at 120 V4 A
Switching current at 125 V0.3 A
Switching current at 220 V0.11 A
Switching current at 230 V3 A
3RB3143-4XB0 — Connection & Mounting
ParameterValue
Mounting / fastening methodContactor mounting
Mounting positionany
Main-circuit connector arrangementTop and bottom
Auxiliary/control circuit connection typescrew-type terminals
Removable aux./control terminalYes
Conductor cross-section: solid1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
Conductor cross-section: solid or stranded1x (0,5 ... 4 mm²), 2x (0,5 ... 2,5 mm²)
Conductor cross-section: finely stranded with ferrule1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Conductor range (AWG), auxiliary contacts2x (20 ... 14)
3RB3143-4XB0 — Environmental
ParameterValue
Operating temperature-25 ... +60 °C
Storage temperature-40 ... +80 °C
Transport temperature-40 ... +80 °C
Relative humidity, operating10 ... 95 %
Max. installation altitude2 000 m
Shock resistance8g / 11 ms
3RB3143-4XB0 — Mechanical
ParameterValue
Width70 mm
Height106 mm
Depth124 mm

Product details

SIRIUS solid-state overload relay, S3 frame, 115 A continuous

The 3RB3143-4XB0 is a SIRIUS solid-state overload relay in the S3 size, rated for a thermal current of 115 A at 480 V and 600 V. It mounts directly onto a contactor via the fastening method, saving DIN-rail space in a packed enclosure. Trip class is field-adjustable across CLASS 5E, 10E, 20E and 30E, so you can match the relay's response to the motor start profile — fast trip for short-acceleration loads, slower for high-inertia starts — without swapping hardware.

Panel fit and termination

Footprint is 70 mm wide, 106 mm tall, and 124 mm deep — the S3 frame fits alongside the matching SIRIUS contactor range. The screwdriver spec calls for a PZ2 Pozidriv tip with a 5-6 mm shaft diameter — keep that bit in your panel kit.

Storage and transport limits are -40 to +80 °C. Vibration resistance is 1-6 Hz at 15 mm amplitude and 6-500 Hz at 20 m/s² for 10 cycles; shock resistance is 8g for 11 ms on the signaling contact in tripped position. That passes the typical IEC 60068-2-27 profile for industrial cabinet gear. Power dissipation per pole is 1.53 W — at 115 A continuous, three poles generate about 4.6 W total. That's low enough that you don't need forced cooling in a standard IP54 enclosure, but keep it away from heat-sensitive components on the same DIN rail.

No stock-holding claim — quoted per RFQ.

Frequently asked questions

What is the 3RB3143-4XB0 used for?

It is a solid-state overload relay for motor protection in the SIRIUS range, rated 115 A thermal current with adjustable trip classes 5E, 10E, 20E, and 30E. It mounts directly onto a contactor and protects the motor against overcurrent conditions without the thermal fatigue of bimetallic designs.

What does the note 'for message tripped' mean on the 3RB3143-4XB0?

The note indicates that the relay provides a dedicated signaling contact (terminals 97/98) that changes state when the overload trips. This contact can be wired to a PLC input or annunciator to indicate a tripped condition remotely.

How can I order the 3RB3143-4XB0 or check availability?

No stock-holding claim is made here.

MPN
3RB3143-4XB0