Skip to main content
Siemens 3RF2350-1AA02 — Solid State Relays

Siemens 3RF2350-1AA02 SIRIUS solid-state contactor, 50 A AC-

MPN3RF2350-1AA02
Active

Siemens SIRIUS 3RF2350-1AA02, single-phase solid-state contactor, 50 A AC-51, 24...230 V AC control, zero-point switching, screw terminals, DIN-rail mount.

$262.14Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RF2350-1AA02 — Identification
ParameterValue
Product designationsolid-state contactor
3RF2350-1AA02 — Contacts & Poles
ParameterValue
Main circuit poles1
Main NO contacts (count)1
Auxiliary NO contacts (count)0
Auxiliary NC contacts (count)0
3RF2350-1AA02 — Coil
ParameterValue
Control supply voltage typeDC
3RF2350-1AA02 — Timing
ParameterValue
ON-delay time1 ms; additionally max. one half-wave
OFF-delay time1 ms; additionally max. one half-wave
3RF2350-1AA02 — Connection & Mechanical
ParameterValue
Fastening / mounting methodscrew fixing and snap-on mounting on standard mounting rail 35 mm according to IEC 60715

Product details

The 3RF2350-1AA02: The 50 A AC-51 rating governs resistive loads — heaters, ovens, incandescent lamp banks. AC-51 is the least demanding duty class; for motor or transformer loads you derate significantly. The UL 508 listing at 45 A tells you the part is accepted for US panel builds. Minimum operational current is 500 mA — below that the thyristor may not latch cleanly. The I²t value of 6600 A²·s is the fuse coordination number: pair with the recommended NEOZED fuse 5SE2335 for semiconductor protection.

Side-by-side mounting is permitted — no mandatory spacing gap, which saves rail space. Dimensions: 67 mm wide, 100 mm tall, 141 mm deep. Main circuit uses screw-type terminals accepting 1.5...6 mm² solid or stranded; control circuit terminals accept 1x 0.5...2.5 mm² or 2x 0.5...1.0 mm² solid. Pollution degree 3 (conductive pollution, typical for industrial control panels). Rated insulation voltage 600 V.

Frequently asked questions

What are the key ratings that determine fit?

50 A AC-51 (resistive load), 45 A UL 508, 24...230 V AC control voltage, minimum operational current 500 mA, I²t 6600 A²·s for fuse coordination, power dissipation 54 W at rated load, derating above 40 °C.

What compliance documentation does this part carry?

Substance prohibition date 07/01/2006 indicates RoHS compliance. UL 508 rating of 45 A confirms UL acceptance. Rated insulation voltage 600 V, pollution degree 3.

Does the 3RF2350-1AA02 mount on a standard DIN rail?

Yes, snap-on mounting on 35 mm DIN rail per IEC 60715, plus screw fixing as an alternative. Side-by-side mounting is allowed with no spacing gap.

What wire sizes does the 3RF2350-1AA02 accept?

Main circuit screw terminals: 1.5...6 mm² solid or stranded. Control circuit screw terminals: 1x 0.5...2.5 mm² or 2x 0.5...1.0 mm² solid.

MPN
3RF2350-1AA02