Rating and load type
The 3RF3320-2AA06 is a 1-pole SIRIUS 3RF33 solid-state contactor rated 20 A in AC-1 duty (resistive load) at 40 °C ambient. That AC-1 figure governs switching of heaters, lighting banks, and transformer primaries — not motor starts. For inductive motor loads you derate to the AC-3 curve, which this part's datasheet defines separately; the 20 A AC-1 number is the ceiling for purely resistive circuits.
Control and termination
Coil is 24 V DC, so it drops into a standard 24 VDC control bus without an extra power supply rail. The load-side voltage range spans 48–600 V AC, covering 48 V, 120 V, 230 V, 277 V, 400 V, and 480 V line voltages without a tap change.