The contact arrangement is 2 normally-open and 2 normally-closed instantaneous contacts, with no leading, lagging, or make-before-break options — a straightforward 2+2 configuration for standard interlocking or status feedback.
The 24 VDC coil draws 3.2 W during both pick-up and hold — no inrush spike to stress a DC supply, but the steady-state draw is constant, so budget that wattage in your 24 VDC bus calculation. Switching capacity varies by voltage: at 110 V it's rated 1 A, at 230 V it's 6 A, and at 400 V it drops to 3 A. The 10 A AC-12 rating is the maximum at 24 V rated value — for higher voltages the contacts derate significantly, so verify against your actual load voltage, not just the coil voltage. Contact reliability is specified as one incorrect switching operation per 100 million at 17 V, 1 mA — this is a dry-circuit rating, meaning the contacts are reliable even at low signal levels without needing a minimum wetting current.
Depth is 72 mm, which includes the coil terminals — account for that when spacing the panel door or adjacent components. Terminals accept solid conductors: 2x 0.5–1.5 mm², 2x 0.75–2.5 mm², or 2x 4 mm². That covers most control wiring sizes; for 4 mm² you'll need a ferrule or direct insertion. The screw-clamp design is standard for the SIRIUS family.