Its 24 VDC coil draws 3.2 W during both closing and holding, so the power supply sizing is straightforward — no inrush peak to budget for. The contact block carries 2 NO instantaneous contacts and 2 NC contacts, rated 10 A at AC-12 (resistive) and 6 A at 230 V, 3 A at 400 V, 1 A at 690 V. That means it handles typical 24 VDC pilot-duty loads easily, and the 690 V rating covers most 3-phase control circuits without derating concerns.
Wiring and compliance
Surge voltage resistance rated at 6 kV, which aligns with IEC 60947-1 overvoltage category III for industrial control circuits. The part carries the SIRIUS brand and is designed for use with Siemens S00 contactor systems.