It carries 3 normally-open and 1 normally-closed instantaneous contacts, rated for 10 A at 24 V and 6 A at 230 V, with a rated insulation voltage of 400 V at 50 Hz and 400–440 V at 60 Hz. The 6 kV rated surge voltage resistance gives it adequate clearance for 400 V line applications without external suppression.
Fastens via screw and snap-on mounting onto a DIN rail, occupying a 45 mm wide footprint with 57.5 mm height and 72 mm depth. Terminals accept solid conductors: 2× (0.5–1.5 mm²), 2× (0.75–2.5 mm²), or 2× 4 mm², covering the common control-wiring gauges for a Size S00 contactor stack.
The 3 normally-open and 1 normally-closed contacts are rated for AC switching at 50/60 Hz: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, 2 A at 500 V, and 1 A at 690 V. DC ratings are lower: 1 A at 110 V and 0.27 A at 220 V.
Shock resistance: 10g at 5 ms and 5g at 10 ms.