It carries 3 normally-open instantaneous contacts and no delayed or lagging contacts, so it closes and opens in step with the coil, not on a timer. Rated 10 A in AC-12 duty (resistive loads at 400 V, 50 Hz), it handles pilot-duty and logic-level switching inside a panel without needing an interposing relay.
Size S00 footprint — 45 mm wide, 57.5 mm tall, 72 mm deep — and dual mounting: screw-fix or snap onto a 35 mm DIN rail.
Contact ratings and wiring
Three NO contacts rated 10 A at 24 V, 1 A at 110 V, and 0.27 A at 220 V — the voltage derating curve matters if you're switching 120 V pilot lights or 24 VDC PLC inputs on the same block. The AC-12 maximum of 10 A at 400 V (50 Hz) is the resistive load ceiling; for inductive or motor loads, derate per the contactor's utilization category. Wire range accepts 2x 0.5–1.5 mm² solid, 2x 0.75–2.5 mm², or 2x 4 mm² — spring-cage terminals, strip to 8 mm.