It carries 4 normally-open instantaneous contacts, rated 10 A in AC-12 duty (resistive/control loads). The 24 VDC coil draws a constant 3.2 W for both pick-up and hold, so there is no inrush spike to size your DC supply around.
Contact ratings — what the numbers mean
For inductive DC switching the numbers drop fast: 1 A at 110 V, 0.27 A at 220 V.
Screw and snap-on mounting onto DIN rail — the same 45 mm width as a S00 contactor, so it lines up mechanically. That matters when you are squeezing it into a crowded panel and the rail is not perfectly horizontal. The screw terminals accept 2x 4 mm² solid or 2x 2.5 mm² stranded — sized for control-circuit wiring, not power feed.
Pollution degree 3 (conductive pollution, typical for industrial control panels). Shock rated at 10g / 5 ms and 5g / 10 ms. RoHS compliance date is July 1, 2006 — the part meets the original RoHS directive.