It carries 3 normally-open (NO) instantaneous contacts rated 10 A at 24 V. The coil operates at 50/60 Hz with a rated control supply voltage of 24 V. Screw and snap-on fastening mounts it directly to a DIN rail. The contactor's mechanical life is typical 30 million operations, with contact reliability specified as one incorrect switching per 100 million operations at 17 V, 1 mA.
Mounting position allows ±180° rotation on a vertical surface and ±22.5° tilt forward/backward, giving flexibility in tight panel layouts. Spring-cage terminals accept 0.25 to 2.5 mm² solid or ferruled stranded wire — strip length should match the terminal design for reliable connection. Operating temperature range is -25 to +60 °C; storage and transport range is -55 to +80 °C. Shock resistance is 10g at 5 ms and 5g at 10 ms.
Switching Ratings by Voltage