It carries three normally-open instantaneous contacts (3 NO) with no delayed, lagging, or make-before-break switching — a straightforward signal-level relay for extending PLC outputs, interlocking contactors, or feeding status back to a controller. Rated operational currents span the control-voltage range: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, and 1 A at 690 V, so the contact rating drops as line voltage rises — typical for AC-15 / DC-13 auxiliary duty. The 6 kV surge voltage resistance (impulse withstand) means it holds up on industrial networks with moderate transient exposure.
Dimensions are 73 mm deep, 45 mm wide, 60 mm tall, which is the standard S00 footprint shared across the SIRIUS contactor family.
For compliance documentation: RoHS substance prohibition date is July 1, 2006, so it meets the original RoHS directive.
Contact reliability and endurance
If your application switches millivolt-level signals (e.g., thermocouple or low-level PLC inputs), this rating confirms the contacts won't oxidize into an open circuit. Mechanical endurance is 30 million operations typical, so it outlasts most panel designs. Shock resistance tested at 10g for 5 ms and 5g for 10 ms — sufficient for machine-mounted panels on presses or conveyors.