Skip to main content
Siemens 3RH1131-2AF00-0TK0-ZX95 — Contactors

Siemens 3RH1131-2AF00-0TK0-ZX95 SIRIUS Auxiliary Contactor,

MPN3RH1131-2AF00-0TK0-ZX95

Siemens SIRIUS auxiliary contactor, size S00, 3 NO instantaneous contacts, screw and snap-on mounting, IP20 front, 73 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RH1131-2AF00-0TK0-ZX95 — Identification
ParameterValue
Contactor frame sizeS00
3RH1131-2AF00-0TK0-ZX95 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 110 V1 A
Rated value @ 220 V0.27 A
3RH1131-2AF00-0TK0-ZX95 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz110 V
3RH1131-2AF00-0TK0-ZX95 — Contacts & Poles
ParameterValue
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RH1131-2AF00-0TK0-ZX95 — Connection & Mounting
ParameterValue
Conductor cross-section, solid2x (0.25 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.25 ... 1.5 mm²)
Mounting methodscrew and snap-on mounting
3RH1131-2AF00-0TK0-ZX95 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RH1131-2AF00-0TK0-ZX95 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RH1131-2AF00-0TK0-ZX95 — Mechanical
ParameterValue
Width45 mm
Height60 mm
Depth73 mm

Product details

SIRIUS auxiliary contactor, size S00

It is rated for 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, and 1 A at 690 V, covering the control-circuit switching range across common AC voltage levels. The contact reliability spec — one incorrect switching operation per 100 million operations at 17 V, 1 mA — means it handles low-energy PLC and sensor signals without the contact wetting issues that plague general-purpose relays. The 45 mm width and 73 mm depth fit the standard S00 footprint, and the screw and snap-on fastening lets it clip directly onto a DIN rail or be panel-screwed — useful when a panel builder wants to pre-wire the contactor on the bench before snapping it into the enclosure.

The substance prohibition date of 07/01/2006 aligns with the original EU RoHS directive, so the contactor complies with RoHS requirements for the substances restricted as of that date.

Mounting position is flexible: the contactor can be rotated ±180° on a vertical surface and tilted forward or backward by ±22.5°, which helps when routing wires in a crowded panel. The operating temperature range is -25 to +60 °C, and storage/transport range extends to -55 to +80 °C. Shock resistance is rated at 10g for 5 ms and 5g for 10 ms, covering the vibration environment of most industrial control panels mounted on machinery. The solid wire capacity is 2x (0.25 to 2.5 mm²), accepting two conductors per terminal — typical for daisy-chaining control voltage to multiple contactors in a motor control center.

Frequently asked questions

Where can I buy 3RH1131-2AF00-0TK0-ZX95 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the contact configuration on 3RH1131-2AF00-0TK0-ZX95?

It carries three normally-open instantaneous contacts with no delayed, lagging, or make-before-break switching elements.

What compliance documentation does this part carry?

The substance prohibition date of 07/01/2006 confirms RoHS compliance for the original directive. The IP20 front protection, surge voltage resistance of 6 kV, and degree of pollution 3 rating indicate it meets IEC 60947-series standards for auxiliary contactors.

Will 3RH1131-2AF00-0TK0-ZX95 drop into a panel specified around 3RH2131-2AK60?

Both are S00 frame size auxiliary contactors with the same 45 mm width and 73 mm depth, so the physical footprint is identical. The key difference is contact configuration: this part has 3 NO contacts, while the 3RH2131-2AK60 carries a different NO/NC count. Check your schematic for the required contact arrangement before substituting.

MPN
3RH1131-2AF00-0TK0-ZX95