Auxiliary contactor for control-circuit switching
Its 10 A rating at 24 V covers typical PLC and relay coil loads; derate to 6 A at 230 V and 3 A at 400 V for higher-voltage control circuits.
Pollution degree 3 rating confirms it tolerates conductive dust and humidity typical of industrial control rooms.
Contact ratings and reliability
Three instantaneous NO contacts rated for AC-15 and DC-13 switching. At 24 V the contact carries 10 A; at 110 V it drops to 1 A; at 220 V to 0.27 A; at 230 V to 6 A; at 400 V to 3 A; at 500 V to 2 A; at 690 V to 1 A. Surge voltage resistance is 6 kV, adequate for 400 V control circuits with proper surge suppression.
Environmental limits
Shock resistance rated at 10 g for 5 ms and 5 g for 10 ms, covering most industrial vibration profiles without contact chatter.