Auxiliary Contactor for Control Circuit Switching
The 10 A rating at 24 V is the thermal current (Ith) for the auxiliary contacts, governing the continuous current-carrying capacity in a control circuit. For inductive loads like contactor coils or relay coils, derate per the AC-15 or DC-13 duty cycles — the 230 V rating of 6 A and 400 V rating of 3 A reflect the switching capacity under those conditions. The 6 kV surge voltage resistance (rated impulse withstand voltage Uimp) ensures the contactor can handle transient overvoltages common in industrial control panels without flashover.
The contactor accepts solid conductors from 0.25 mm² to 2.5 mm² (2x per terminal), suiting standard control wiring.