The 10 A rated value at 24 V covers most PLC output and relay interface loads; derate to 6 A at 230 V and 3 A at 400 V when switching higher line voltages. Three instantaneous NO contacts (no delayed or lagging switching) give you a clean set of mirror signals for feedback, interlock, or status indication back to the controller.
The spring-cage terminals accept 0.25 to 2.5 mm² solid or stranded wire — strip length around 8 mm for a clean seat under the clamp.